SYSTEM WIRING: AC OUTPUT
INSTALLATION MANUAL
3
Please note that the cabinet door can be unlocked and opened by using the key pro
-
vided along with the product
SYSTEM WIRING: AC OUTPUT
System Wiring: OUT#1 and OUT#2
Figure 5 - Terminal Block for Out#1 and Out#2
The terminal block for Out#1 (PWR-480W) and for Out#2 (Scale) is highlighted in the
picture above.
Use cables 3 X yy mm
2
, where "yy" is a value between 2.5 - 4 mm
2
.
Out#1 and Out#2 are protected by Fuse QF01, 8A gG.
HIGH VOLTAGE: When the main switch is in the OFF position, the outputs
#1, #2, and #3 are disconnected, but not the AC Line Input Terminals!