GWY-01-PBS-01
14
2
2.2 LED INDICATORS
2.2.1 Front Panel LEDs
LED Name
LED Color
LED Description
POWER
GREEN
The POWER LED is ON whenever power
is applied to the Gateway.
BUS
AMBER
The BUS LED will flash ON and OFF to
indicate that data is being transmitted
between the Gateway and one or more
RFID controllers on the Subnet16 network.
SOLID GREEN
The Profibus Mode LED is solid green
when the Gateway Profibus interface is
operational, online and exchanging data.
FLASHING
GREEN
The Profibus Mode LED is flashing green
when the Gateway Profibus interface is
operational and on-line, but idle.
FLASHING RED
(1 FLASH)
The Profibus Mode LED is flashing red
and blinks once when a Profibus
parameterization error has occurred.
PBS MODE
Profibus Mode
FLASHING RED
(2 FLASHES)
The Profibus Mode LED is flashing red
and blinks twice when a Profibus
configuration error has occurred.
SOLID GREEN
The Status LED is solid green when the
Profibus communication is initialized.
FLASHING
GREEN
The Status LED is flashing green when the
Profibus communication is initialized, but a
diagnostic event(s) is present.
PBS STAT
Profibus Status
SOLID RED
The Status LED is solid red when a
Profibus exception error has occurred.
ERROR
SOLID RED
The Error LED is solid red when a
Gateway configuration error has occurred,
i.e. an invalid or unrecognized command.
This LED will be cleared when a valid
command is sent.
Table 1: Front Panel LEDs