S100 SERIES IO-Link

Instruction Manual

CONTROLS

OUTPUT LED – Yellow

The yellow LED indicates the output status.

Please refer to “Settings” for procedure indications during 

acquisition or setting phases.

INSTALLATION

The sensor can be positioned by means 

of the two housing’s threaded holes (M3) 

using two screws (M3x12 or longer or 

M2.5 passing screw, 0.4 Nm maximum 

tightening torque) with washers or by 

mean of the two rear holes using two 

M3 passing screw, 0.4Nm maximum 

tightening torque.

Various  orientable  fixing  brackets  to 

ease the sensor positioning are available 

(please refer to the accessories listed in 

the catalogue).

During installation of transparent models 

(S100-T10) refer to the diagram below 

for proper alignment between sensor and 

reflector.

CONNECTIONS

DIMENSIONS

TECHNICAL DATA

Power Supply

10 ... 30 VDC (Class 2 UL508) (reverse polarity protected)

Ripple

10% max.

Current consumption (output current 

excluded)

30 mA max.

Output

PNP, NPN or Push-Pull (short-circuit protection)

Output current

100 mA max. (total for both outputs), 100 mA max. (for single output)

Output saturation voltage

2 V max.

Input

Pin 2 can be configured as an input through IO-Link. If so, it cannot be kept disconnected

Response time

M10/T10: 1 ms; B10: 500 µs

Switching frequency

M10/T10: 500 Hz; B10: 1kHz

Indicators

Output LED (yellow)

Operating temperature

-25 °C ... +55 °C

Storage temperature

-40 °C ... +70 °C

Operating distance (typical values)

B10: 0.01 ... 4.5 m (on R2 reflector Ø 48mm)

M10: 30…200 mm (on White 90%)

T10: 0.1…2 m (on R2 reflector Ø 48mm)

Optical axis deviation (max.)

5°  mod. T10

Distance object detection

M10: 10…200 mm (on White 90%)

T10: 0.1…2 m (on trasparent object)

Difference on White 90% / Gray 18%

M10: < 23% at 200 mm

Hysteresis on White 90%

M10: < 20 mm at 200 mm

Emission type

Red LED (632 nm) mod.B10, Infrared LED (860 nm) mod.T10/B10

Exempt Risk Group (RG0) for IEC 62471

Ambient light rejection

according to EN 60947-5-2

Vibration

0.5 mm amplitude, 10 … 55 Hz frequency, for every axis (EN60068-2-6)

Shock resistance

11 ms (30 G) 6 shock for every axis (EN60068-2-27)

Housing

ABS body / indicators cover PMMA

Lenses

PC lens / window PMMA

Mechanical protection

IP67

Connections

M8 4-pole connector

Weight

10 g.

SETTINGS

The N.C. output can be configured through IO-Link as a REMOTE input (M10/T10) or as 

a L/D input. Set the input through IO-Link and follow the instructions. The input cannot be 

kept disconnected.

LIGHT/DARK INPUT (S100-B10)

The L/D input allows the operator to select the DARK/LIGHT operating mode as follows:

- pin 2 connected to: 0V = DARK mode, +Vcc = LIGHT mode.

Alignment S100-B10

Position the sensor and reflector on opposite sides. Find the points where the yellow LED 

(OUT) is switched ON and OFF in both vertical and horizontal positions and fix the sensor in 

the centre between these points.

REMOTE input (external Teach-in) S100… M10/T10

The REMOTE input sets the background suppression operating distance for M10 and the 

reading sensitivity for T10 using two different acquisition procedures:

S100-M10

Object acquisition (to be used in case of absence of the background)

1. Place the target opposite the sensor at the maximum distance required;

2. Connect the REMOTE wire to + VDC for 1 second. The OUT LED changes its status once.

If the object is out of range the sensor fails the acquisition and the OUT LED blinking. To 

return at normal operation, connect the VDC for 100ms.

Acquisition for background suppression

1. 

Place the sensor in front of the background within the maximum operating distance.

2. Connect the REMOTE wire to +VDC for 3 seconds.The OUT LED changes its status

twice. If the object is out of range the sensor fails the acquisition and the OUT LED

blinking. To return at normal operation, connect the VDC for 100ms.

S100-T10

Reflector standard acquisition

1. 

Position the reflector in front of the sensor at the required distance (within the operating 

range).

2. Connect the REMOTE wire to +VDC for 1 second. The OUT LED changes its status once.

If the reflector is outside the operation range, the sensor fails the acquisition and the OUT 

LED blinks. To go back to the condition before the acquisition, connect the REMOTE wire to 

+VDC for at least 100 msec.

Reflector acquisition at maximum sensitivity

This procedure allows to obtain a more precise alignment between sensor and reflector, in 

particular for longer reading distances:

1. Connect the REMOTE wire to +VDC for 3 seconds. The OUT LED changes its status 

twice: the sensor is at maximum sensitivity.

2. 

Position  the  reflector  in  front  of  the  sensor  (within  the  operating  range),  vertically  and 

horizontally determine the OUT LED switching on and off points, and secure the reflector 

in the centre between such points.

3. Connect the REMOTE wire to +VDC for 1 second. The OUT LED changes its status once.

LIGHT/DARK selection (S100…M10/T10)

To  change  the  operating  DARK/LIGHT  mode  connect  the  REMOTE  wire  to  +VDC  for  7 

seconds until the LED OUT changes its status three times.

The sensor blinks and switches the operating mode (LIGHT → DARK, DARK → LIGHT) 

and saves it in memory.

R1

Ø 23

mm

R2

Ø 48

mm

R3

18x54

mm

R4

47x47

mm

R5

Ø 75

mm

R6

36x55

mm

RT3970

60x40

mm

B10

0.02...2

0.01...4.5

0.01...3

0.01...4.5 0.01...5.5

0.01...4 0.05...1.8

T10

0.1...1

0.1...2

0.1...1

0.1...2 0.1...2.5 0.1...2

0.1...0.8

TAB.1: Operating distances for B10 and T10 models (m)

AVAILABLE REFLECTORS

Sensors  are  NOT  safety  devices,  and  MUST  NOT  be  used  in  the  safety 

control of the machines where installed.

Datalogic S.r.l.

Via S. Vitalino 13 - 40012 Calderara di Reno - Italy

Tel: +39 051 3147011 - Fax: +39 051 3147205 - www.datalogic.com

Helpful links at www.datalogic.com: 

Contact Us, Terms and Conditions, Support.

The warranty period for this product is 36 months. See General Terms and Conditions of 

Sales for further details.

For information about the disposal of Waste Electrical and Electronic Equipment 

(WEEE), please refer to the website at 

www.datalogic.com

.

© 2020 Datalogic S.p.A. and/or its affiliates - ALL RIGHTS RESERVED. - Without limiting 

the rights under copyright, no part of this documentation may be reproduced, stored 

in or introduced into a retrieval system, or transmitted in any form or by any means, or 

for any purpose, without the express written permission of Datalogic S.p.A. and/or its 

affiliates.  Datalogic  and  the  Datalogic  logo  are  registered  trademarks  of  Datalogic  S.p.A. 

in many countries, including the U.S.A. and the E.U. All other trademarks and brands are 

property of their respective owners. Datalogic reserves the right to make modifications and 

improvements without prior notification.

821006941

 

Rev. B

Dimensions in mm

Summary of Contents for IO-Link S100 Series

Page 1: ...T LED changes its status once If the object is out of range the sensor fails the acquisition and the OUT LED blinking To return at normal operation connect the REMOTE VDC for 100ms Acquisition for bac...

Page 2: ...tivo 2 Collegare il filo REMOTE a Vcc per 1 s Il LED OUT cambia stato 1 volta Se l oggetto fuori dal campo operativo il sensore fallisce l acquisizione e il LED OUT lampeggia Per tornare in funzioname...

Page 3: ...LED OUT blinkt Zur R ckkehr zum Normalbetrieb REMOTE mindestens 100 ms lang mit VDC verbinden Erfassung f r Hintergrundausblendung 1 Den Sensor vor dem Hintergrund platzieren innerhalb der maximalen...

Page 4: ...est hors de port e le d tecteur ne peut pas effectuer l acquisition et la LED DE SORTIE clignote Pour revenir au mode de fonctionnement normal relier REMOTE Vcc pendant au moins 100ms Acquisition pour...

Page 5: ...REMOTE S100 M10 T10 REMOTE M10 T10 S100 M10 1 2 REMOTE VDC 1 OUT LED OUT LED REMOTE VDC 100ms 1 2 REMOTE VDC 3 OUT LED OUT LED REMOTE VDC 100ms S100 T10 1 2 REMOTE VDC 1 OUT LED OUT LED REMOTE VDC 100...

Page 6: ...el index 0x3A System Parameters Index dec Parameter Object Name Lenght Subindex offset Value Range Description Data Type Access 0x000C 12 Device Access Locks 2 octets Bit 1 Data Storage 0 unlocked 1 l...

Page 7: ...perature 2 octets 2 octets 2 octets 2 octets 2 octets 1 64 2 48 3 32 4 16 5 0 Device temperature actual Device min temperature since powerup Device max temperature since powerup Device min temperature...

Page 8: ...distance M10 Switching threshold B10 T10 UIntegerT R W Saved in non volatile memory B10 T10 setting a higher threshold reduces the operating distance progressively to 0 output always active 0x003F 63...

Page 9: ...t type Device status Remarks 0x4220 16928 Temperature underrun Appears Disappears Warning Out of specification 0x4210 16912 Temperature overrun Appears Disappears Warning Out of specification 0x5100 2...

Page 10: ..._1 ISDU ISDU 0xC 0x3A 0x000C 12 2 1 0 1 0 1 2 3 4 15 RecordT R W 0x000D 13 2 2 2 2 2 2 0x0001 0x8000 0x8001 0x8003 0x8004 0x8007 SSC UIntegerT16 ArrayT RO 0x000E 14 PDInput 3 3 3 3 0x01 0x01 0x00 0x01...

Page 11: ...0 0 StringT RO 0x0018 24 32 B10 T10 StringT R W 0x0028 40 1 PDin RO 0x0052 82 2 2 2 2 2 1 64 2 48 3 32 4 16 5 0 IntegerT IntegerT IntegerT IntegerT IntegerT RO RO RO RO RO 0x0053 83 2 2 1 16 2 0 B10...

Page 12: ...T10 UIntegerT 0x003E 62 SSC2 2 2 1 16 2 0 0 3983 M10 210 1982 B10 177 1783 T10 M10 B10 T10 UIntegerT R W B10 T10 0 0x003F 63 SSC2 1 1 1 24 2 16 0x00 B10 T10 0x01 M10 0x01 DO UIntegerT UIntegerT R W T1...

Page 13: ...B10 T10 SSC1 SSC2 RGB B10 T10 WO 0x0002 2 1 0xA5 165 WO 0x0002 2 Ping 1 0xAF 175 LED WO 0x4220 16928 0x4210 16912 0x5100 20736 0x7710 30480 0x8C40 35904 B10 ID S100 PR 5 B10 OZ 10001 S100 PR 5 T10 OZ...

Page 14: ...DR CKLICHEN STILLSCHWEIGENDEN GESETZLICHEN ODER GARANTIE Datalogic garantit que les Produits seront exempts de d fauts de mat riaux et de fabrication dans le cadre d une utilisation normale et appropr...

Page 15: ...ahmen zu ergreifen FR Conformit CE La marque CE indique la conformit du produit aux exigences essentielles nonc es dans la directive europ enne applicable Les directives et les normes applicables sont...

Page 16: ...sor in the centre between these points Acquisition with REMOTE external Teach in S100 Mx0 Tx0 The REMOTE input sets the background suppression operating distance for M00 M10 and T00 T10 using two diff...

Page 17: ...due unit al centro fra i punti rilevati Acquisizione con REMOTE Teach in esterno S100 Mx0 Tx0 L ingresso REMOTE permette di settare la distanza operativa dei modelli M00 M10 e T00 T10 mediante due pr...

Page 18: ...externe S100 Mx0 Tx0 L entr e REMOTE permet de r gler la port e op rationnelle des mod les M00 M10 et T00 T10 en utilisant deux proc dures d acquisition diff rentes S100 M00 M10 L acquisition de l obj...

Page 19: ...ei den Modellen M00 und M10 werden zwei Erfassungsverfahren unterschieden S100 M00 M10 Objekterfassung im Falle der Abwesenheit des Hintergrund verwendet warden 1 Das zu erfassende Objekt in gew nscht...

Page 20: ...ww datalogic com Contact Us Terms and Conditions Support The warranty period for this product is 36 months See General Terms and Conditions of Sales for further details For information about the dispo...

Page 21: ...Link utili disponibili su www datalogic com Contatti Termini e Condizioni Supporto Il periodo di garanzia per questo prodotto di 36 mesi Per maggiori dettagli vedere Condizioni Generali di Vendita Per...

Page 22: ...lgemeine Verkaufsbedingungen Informationen zur Entsorgung von Elektro und Elektronik Altger ten WEEE erhalten Sie auf der Webseite www datalogic com 2020 Datalogic S p A und oder die Tochtergesellscha...

Page 23: ...duit est de 36 mois Voir les Conditions G n rales de Vente sur www datalogic com pour plus de d tails Pour toute information relative l limination des d chets lectroniques WEEE veuillez consulter le s...

Page 24: ...0947 5 2 0 5 mm 10 55 Hz EN60068 2 6 11 ms 30 G 6 EN60068 2 27 ABS PMMA PMMA PC IP67 M8 4 12 g S100W REMOTE REMOTE IO Link IO Link REMOTE Datalogic S r l Via S Vitalino 13 40012 Calderara di Reno Ital...

Page 25: ...index 0x3A Emitter Status index 0x51 System Parameters Index dec Parameter Object Name Lenght Subindex offset Value Range Description Data Type Access 0x000C 12 Device Access Locks 2 octets Bit 1 Dat...

Page 26: ...UIntegerT RO 0x0052 82 Device Temperature 2 octets 2 octets 2 octets 2 octets 2 octets 1 64 2 48 3 32 4 16 5 0 Device temperature actual Device min temperature since powerup Device max temperature sin...

Page 27: ...nfig 1 octet 1 octet 1 24 2 16 0x00 High Active default 0x01 Low Active 0x01 Single Point default DO pin configuration UIntegerT UIntegerT R W Saved in non volatile memory 2 octets 3 0 0 2 Hysteresis...

Page 28: ...m device temperature since powerup Maximum device temperature since powerup Device Status Detailed Device Status WO 0x0002 2 Disable enable emission 1 octet 0xB0 176 Toggle emission enable disable emi...

Page 29: ...2_1 ISDU ISDU 0xC 0x3A 0x51 0x000C 12 2 1 0 1 0 1 2 3 4 15 RecordT R W 0x000D 13 2 2 2 2 2 2 0x0001 0x8000 0x8001 0x8003 0x8004 0x8007 SSC UIntegerT16 ArrayT RO 0x000E 14 PDInput 3 3 3 0x01 0x01 0x00...

Page 30: ...0x001A 26 32 StringT R W 0x0028 40 1 PDin RO 0x0041 65 2 UIntegerT RO 0x0052 82 2 2 2 2 2 1 64 2 48 3 32 4 16 5 0 IntegerT IntegerT IntegerT IntegerT IntegerT RO RO RO RO RO 0x0053 83 2 2 1 16 2 0 In...

Page 31: ...00 0x01 0x01 C Q UIntegerT UIntegerT R W 2 3 0 0 2 UIntegerT 0x003E 62 SSC2 2 2 1 16 2 0 280 1950 UIntegerT R W 0x003F 63 SSC2 1 1 1 24 2 16 0x00 0x01 0x01 DO UIntegerT UIntegerT R W 2 3 0 0 2 UIntege...

Page 32: ...x4B 75 WO 0x0002 2 1 0x4F 79 WO 0x0002 2 1 0x82 130 SSC1 SSC2 RGB WO 0x0002 2 1 0xA5 165 WO 0x0002 2 1 0xB0 176 WO 0x0002 2 Ping 1 0xAF 175 LED WO 0x4220 16928 0x4210 16912 0x5100 20736 0x7710 30480 I...

Page 33: ...DR CKLICHEN STILLSCHWEIGENDEN GESETZLICHEN ODER GARANTIE Datalogic garantit que les Produits seront exempts de d fauts de mat riaux et de fabrication dans le cadre d une utilisation normale et appropr...

Page 34: ...ahmen zu ergreifen FR Conformit CE La marque CE indique la conformit du produit aux exigences essentielles nonc es dans la directive europ enne applicable Les directives et les normes applicables sont...

Reviews: