ELECTRICAL CONNECTIONS
76
MATRIX 220
ID-NET Cables
The following instructions are referred to Figure 52, Figure 53 and Figure 54.
•
The general cable type specifications are: CAT5 twisted pair + additional CAT5
twisted pair, shielded cable AWG 24 (or AWG 22) stranded flexible.
We recommend using DeviceNet cables (drop or trunk type) to the following refer-
ence standards:
AN50325 – IEC 62026
UL STYLE 2502 80°C 30V
•
Cable Shield MUST be connected to earth ground ONLY at the Master.
•
NEVER use ID-NET cable shield as common reference.
•
The ID-NET max cable length depends on the baudrate used, (see the Baudrate
Table below).
•
For Common Power Connections use only 2 wires (ID+ and ID-).
- DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do
not put it together with AC cable):
- Wire dimensioning must be checked in order to avoid voltage drops greater than
0.8 Volts.
- Cable should lie down as near as possible to the ID-NET cable (avoiding wide
loops between them).
•
Reader's chassis may be connected to earth.
•
Network inside the same building.
Baudrate Table
Baudrate
125 kbps
250 kbps
500 kbps
1 Mbps
Cable Length
1200 m
900 m
700 m
*
* Application dependent, contact your Datalogic representative for details.
NOTE
The default ID-NET baudrate is 500 kbps. Lower ID-NET baudrates allow
longer cable lengths.
Summary of Contents for Matrix 220
Page 1: ...Matrix 220 PRODUCT REFERENCE GUIDE Image Based Reader...
Page 18: ...GENERAL VIEW xviii MATRIX 220...
Page 102: ...ELECTRICAL CONNECTIONS 84 MATRIX 220 Figure 57 NPN External Trigger Using Matrix 220 Power...
Page 163: ...PASS THROUGH CONFIGURATIONS PRODUCT REFERENCE GUIDE 145...
Page 171: ...INTERNAL NETWORK CONFIGURATIONS PRODUCT REFERENCE GUIDE 153...
Page 173: ...INTERNAL NETWORK CONFIGURATIONS PRODUCT REFERENCE GUIDE 155 Open the cloned application job...
Page 211: ......