SE-SR2
Operating instructions SE-SR2
826002433-EN-Rev.C
12
CH.2
Safety contacts of channel 2 are closed.
Faults – Interference
}
Earth fault: The supply voltage fails and the safety contacts open. Once the cause of
the respective fault has been rectified and the supply voltage is switched off for approx.
1 minute, the unit is ready for operation again.
}
Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.
}
LED "POWER" does not light: Short circuit or no supply voltage.
Dimensions in mm
Technical details
General
Approvals
CE, TÜV, cULus Listed
Electrical data
Supply voltage
Voltage
24 V
Kind
DC
Voltage tolerance
-15 %/+10 %
Output of external power supply (DC)
2 W
Residual ripple DC
160 %
Duty cycle
100 %
Max. inrush current impulse
Current pulse, A1
1,7 A
Pulse duration, A1
3,3 ms
Inputs
Number
2