Instruction Manual
SG2 EXTENDED
33
6.2. Test
function
The TEST function can be activated by keeping a normally open external contact (TEST push-button),
open for at least 0.5 seconds.
The TEST signal is active high.
6.3. Reset
function
The RX light curtain has a RESET function which is activated after an internal error. The reset can be
made only in case of optical error, OSSD error EDM or manual/automatic restart selection (See
chapter 7 “
Diagnostic Functions
”),.
The RESET function can be activated by keeping a normally open external contact
(RESET/RESTART push-button), open for at least 5 seconds.
The RESET signal is active high.
Safety light curtain status
Faulty block
Standard
24 VDC
0 V