91
PLC SAFETY DIAGRAM
INTERLOCK_A INTERLOCK_B INT_OUT_A
INT_OUT_B
CONDITION
OPEN
OPEN
CLOSED
CLOSED
SAFE
CLOSED
OPEN
CLOSED
OPEN
DANGEROUS
OPEN
CLOSED
OPEN
CLOSED
DANGEROUS
CLOSED
CLOSED
OPEN
OPEN
DANGEROUS
Truth table under normal conditions.
COMPONENT CHARACTERISTICS
DOOR SWITCH:
SAFETY SWITCH, designed in compliance with the standard currently in effect IEC60947,
EN292, EN60204, EN1088. Two redundant contacts. IP67. B10d=2000000.
SAFETY LOGIC:
main component SAFETY PLC min. PLd according EN13849-1. Output type relays, min
10mA. To be installed in an IP54 enclosure.
CONCLUSIONS
Because MTTFd is greater than 100 years, Category is 3, max achievable DC is 99%, so this example
satisfies the PLr=c.