V180808N
iBB-DC8 Manual
Page 12
8. Basic Operation
8.1.
Web Interface
The iBootBar web interface provides the
easiest means of operating the outlets and
monitoring the current status of the units.
One or more outlets can be
simultaneously controlled with a few
mouse clicks. In cluster configurations, all
128 outlets can be managed from the web
pages.
The interface is divided into three sections
Header, Control, and Status.
Each user will only be able to view and
control the outlets, devices and groups
that have been assigned to the user.
Note: Current sensing is available only on the A/C versions of iBootBar. Ignore current reporting for DC
Versions.
Header The Header identifies the iBootBar currently being accessed. If multiple iBootBars are deployed in a
cluster configuration, this will be the master iBootBar.
The Header allows the selection of various status views. To select an individual iBootBar, or predefined group
of outlets, click on the one of the two dropdown lists. To select the global view, click on Global. To see the
status of the AutoPing feature, click on AutoPing.
Control The Control panel provides the clickable buttons to change status of one or more
outlets. Once one or more outlets have been selected, click on the On, Off, or Cycle
button. Cycle will perform a timed change in outlet state; either Reboot (On-Off-On), or
Cycle (Off-On-Off) depending on the current state of the outlet.
The Cycle timer box allows selection of the length, in seconds, of all cycle or reboot
operations. Entries of 1 to 99 seconds are valid.
The Delay timer box allows selection of the delay time, in seconds, between the turning
on of each outlet whenever more than one outlets are turned on from the same
command. This can be used to prevent over-current draw on initial power up of devices.
Entries of 0 to 99 seconds are valid.
The Select All and Select None buttons allow selection or de-selection of all outlets.
Refresh provides an update of the status page to display current conditions. Web pages
are static moments in time, so use the Refresh obtain the latest status.
Logout terminates the session.