iBootBar 

– Precision Version 

 

   

Page 15 

iBootBar_Precision_20160428e.doc 

 

Firmware ver 1.41.32 

 

  

AutoPing 

The AutoPing feature allows iBootBar to automatically detect failed equipment and perform a timed reboot or other 
power  control  function  (like  turning  on  an  indicator  or  siren).    You  set  any  IP  address  to  be  periodically  pinged.  
When iBootBar no longer detects a response from the address, the programmed power control function is actuated. 
 
Up to eight IP addresses can be monitored by AutoPing.  Each AutoPing monitor is assigned to an outlet. 
 

Ping Address

  Enter the IP address of the device to be pinged.   

 

Ping Frequency

  Enter 1 to 999 seconds.  The ping will go out to the selected device this often. 

 

Fail Counter

  Enter 1-99 times the ping needs to fail consecutively before the selected action is taken.  When the 

fail count has been reached, the AutoPing action will be triggered. 
 

Action:

  Select from 

None

 

AutoPing not used

 

On 

– Latch

 

Upon triggering, iBootBar will power on the assigned outlet and remain so 
until changed via the web or telnet/serial interface.

 

On 

– Follow

 

Upon triggering, iBootBar will power on the assigned outlet.  When the ping 
response returns, iBootBar will power the off the outlet

 

Off 

– Latch

 

Upon triggering, iBootBar will power off the assigned outlet and remain so 
until changed via the web or telnet/serial interface.

 

Off 

– Follow

 

Upon triggering, iBootBar will power off the assigned outlet.  When the ping 
response returns, iBootBar will power the outlet on.

 

Cycle

 

Upon triggering, iBootBar will cycle the power to the assigned outlet.  
iBootBar will wait the Ping Frequency x Fail Count; if the response does not 
return, the power will be recycled again.  This will continue until the ping 
response returns or AutoPing is turned off.  Make sure your AutoPing 
frequency x Fail Count is longer than the time required to reboot your device.

 

Cycle Once

 

Upon triggering, iBootBar will cycle power one time. It will not cycle again 
automatically until the ping response returns and is lost again.

 

 

With AutoPing operational, the iBootBar page will display the current status of this feature.  The status will be OK to 
indicate that iBootBar is receiving responses to the ping, or that the fail counter has not yet been exceeded.  Click on 
the Status message to see greater details on the AutoPing status. 
 
If the fail count has been exceeded, the status will change to Triggered.  Click on the Status message to see greater 
details on the AutoPing status. 
 

Email Notification 

Email can be automatically sent for outlet changes, AutoPing triggers and current alarms.   The necessary 
parameters for email are set using the Telnet / Serial Interface: 
 

set email server <dotted decimal> 

set email address <return address 64 char max> 

set email username <user name 128 char max> 

set email password <password 128 char max> 

 

Each user is assigned an email address and email can be turned on or off for that user: 

Summary of Contents for iBootBar iBP-N15

Page 1: ...EMA 20 Amp 8 x NEMA 5 15 IP Control Serial Control Internal Modem iBP 2N20 2 x NEMA 40 Amp 8 x NEMA 5 15 IP Control Serial Control iBP 2N20 M 2 x NEMA 40 Amp 8 x NEMA 5 15 IP Control Serial Control Internal Modem iBP C10 IEC C14 10 Amp 8 x IEC C13 IP Control Serial Control iBP C10 M IEC C14 10 Amp 8 x IEC C13 IP Control Serial Control Internal Modem iBP 2C10 2 x IEC C14 20 Amp 8 x IEC C13 IP Contr...

Page 2: ... 4 Installation 5 Configuration 7 Basic Operation 9 Command Line Interface Direct Messaging Protocols Advanced Operations 14 Frequent Outlet Control Multi Outlet Control DTMF Control AutoPing Email Notification SNMP Firmware Upgrades Password Recovery Appendices Specifications 17 Compliance 18 Modem Certifications 19 SNMP MIB 20 Technical Support Returns Warranty 21 ...

Page 3: ...defeat the safety purpose of the grounding type plug Do not use a 3 to 2 prong adapter at the receptacle use of this type adapter may result in risk of electrical shock and or damage to this product 9 Do not allow anything to rest on the power cord Do not locate this product where the cord will be abused by persons walking on it 10 Do not overload wall outlets and extension cords as this can resul...

Page 4: ...ity The iBP has many features to make the management of power distribution simple and cost effective 8 Independently controllable outlets Dual power inputs for redundant power feeds Support for dual redundant powered devices Naming of outlets for easy identification Multi Outlet control of outlets for simultaneous management Current monitoring with over and under alarm notification Multiple users ...

Page 5: ... the iBP to the standard 19 inch rack Ethernet The iBootBar has a 10 100 Ethernet port The default address is 192 168 0 254 Serial Port The iBootBar has a 9 pin D subminiature connector for RS 232 serial control The connector is configured as DCE for direct connection to a laptop or other terminal device Default serial parameters are 115 200 bps 8 data no parity 1 stop bit 115200 8 n 1 Serial Port...

Page 6: ...imum current load for all outlets cannot exceed 12 Amps at 115VAC or 10 Amps when used at 240VAC The iBP 2C10 M is for international applications and can be used on 100V to 240VAC The iBP 2C10 provides two IEC 320 style universal inlets for connecting a detachable power cord Two standard IEC to CEE7 European cord sets are supplied with the unit for use on 10 Amp 240VAC service The total maximum cu...

Page 7: ...dem 2 Automatically from a DHCP Server 3 ARP Ping To configure the mode to set the IP address access the iBootBar command line interface CLI and use the set ipmode command as indicated below Setting the IP address using CLI The following commands are used to set the IP parameters set ipaddress dotted decimal ex 192 168 0 125 set subnet dotted decimal ex 255 255 255 0 set gateway dotted decimal ex ...

Page 8: ...tted decimal for the iBootBar and the MAC address is the MAC Address of the iBootBar The MAC Address of the iBootBar is located on the rear of the unit Example arp s 63 211 86 165 00 50 c2 05 01 c1 enter new IP addr MAC addr 4 Ping the iBootBar to program the IP address into the iBootBar Type ping IP Address Note If the ping command returns host not responding 4 times then the address has not been...

Page 9: ...cycle The cycle time is the length of the reboot or power on In seconds 0 99 set cycle n get console Display current console configuration set console timeout 30 3600 disable Console can be set to automatically logout with no activity for 30 seconds to 1 hr in seconds or disabled set console baudrate baud 2400 4800 9600 19200 38400 57600 115200 get autologin Enabled will allow admin rights without...

Page 10: ... address of the iBootBar set ipaddress dotted decimal Set the current IP address ipmode must be set to static to use this command set subnet dotted decimal Set the Subnet Mask set gateway dotted decimal Set the Gateway get telnet Display current telnet enable telnet port parameters set telnet enable yes no Enable or Disable Telnet Server set telnet port 1 65535 Change the Telnet Server IP port def...

Page 11: ...ne Byte status for each outlets all 8 Bytes of status for each command Verbose Status for controlled outlet only Basic Syntax esc pass esc outlet cmd esc pass outlet cmd CR iPAL Protocol esc pass esc outlet cmd Syntax definitions esc ASCII Escape Character Decimal 27 Hex 1B pass Password no username is required outlet Outlet number 1 8 A for All outlets cmd Command to be performed Commands E Turn ...

Page 12: ...n Outlet ON C Cycle Outlet Cycle can be On Off On or Off On Off depending on starting status T Set Cycle Time Cycle time in seconds Valid range 1 99 Get Status Outlet number optional No outlet number will respond with status for all outlets Examples esc pass 1ON enter Turn on outlet 1 esc pass 3C enter Cycle Outlet 3 esc pass enter Status for all Outlets esc pass 5 enter Status for Outlet 5 Respon...

Page 13: ...her on or off to improve product life expectancy for example set outlet 1 initial state on set outlet 4 initial state off Multi Outlet Control Command This command is used to operate all eight outlets simultaneously set outlets nnnnnnnn Where n is either 0 for off or 1 for on The command once typed reads from outlet eight to outlet 1 most significant to least significant set outlets 8 status 7 sta...

Page 14: ...he key is used to reboot or power cycle the outlet for the time configured with the CLI command cycle time The new status of the outlet is stated If the key is used the iBootBar will also state begin to indicate the reboot or cycle has begun 5 A new prompt tone will indicate that new commands can be entered While a reboot is in progress additional outlets can be addressed and commanded 6 The calle...

Page 15: ...llow Upon triggering iBootBar will power off the assigned outlet When the ping response returns iBootBar will power the outlet on Cycle Upon triggering iBootBar will cycle the power to the assigned outlet iBootBar will wait the Ping Frequency x Fail Count if the response does not return the power will be recycled again This will continue until the ping response returns or AutoPing is turned off Ma...

Page 16: ...nabled using the set upload enable yes command on the console interface To upgrade the iBootBar download the latest version of the firmware and upgrade utility from the Dataprobe website http Dataprobe com ibootbartools html Password Recovery Holding the reset button on the front panel of the iBootBar for 5 seconds or longer will initiate a password recovery mode Once the reset button is released ...

Page 17: ... M C14 8 x C13 I S M iBP 2C10 2 x C14 8 x C13 I S iBP 2C10 M 2 x C14 8 x C13 I S M iBP C20 C20 8 x C13 I S iBP C20 M C20 8 x C13 I S M iBP 2C20 2 x C20 8 x C13 I S iBP 2C20 M 2 x C20 8 x C13 I S M Key Input N15 NEMA 5 15 Linecord 115VAC 15 Amps combined total switched N20 NEMA 5 20 Linecord 115VAC 20 Amps combined total switched C14 IEC320 C14 Receptacle 100 240VAC 10 Amps total at 240VAC Max C20 ...

Page 18: ...an for help This device complies with Part 15 of the FCC rules Operation of this device is subject to the following conditions 1 This device may not cause harmful interference and 2 this device must accept any interference that may cause undesired operation WARNING Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority t...

Page 19: ...e current country setting Note Use of the wrong countrycode violates local laws and the warranty of this product Country countrycode Argentina 07 Australia 09 Austria 253 Belgium 253 Canada 181 China 181 Cyprus 253 Czech Republic 253 Denmark 253 Finland 253 France 253 Germany 253 Greece 253 Hong Kong 153 Hungary 253 Iceland 253 Indonesia 153 Ireland 253 Italy 253 Japan 00 Korea 181 Liechtenstein 2...

Page 20: ...er32 delayTime 2 TB snmpManagerTable 1 TE snmpManagerEntry 1 RO Integer32 snmpManagerIndex 2 RW DisplayString snmpManagerIPAddress 3 RW INTEGER Enum snmpManagerEnable 3 TB outletTable 1 TE outletEntry 1 RO Integer32 outletIndex 2 RW OCTET STRING outletName 3 RO INTEGER Enum outletStatus 4 RW INTEGER Enum outletCommand 5 RO INTEGER Enum outletAPStatus 4 BR info 1 RO Integer32 currentLC1 2 RO Intege...

Page 21: ...l Dataprobe Technical Service at 201 934 5111 to receive a Return Materials Authorization RMA Number prior to sending any equipment back for repair Include all cables power supplies and proof of purchase with shipment THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORT...

Reviews: