DT80 Range User Manual
Page 399
RG
Error Number – Description
•
Cause/Action
Error Category
Syntax
Operation
Memory
Reading
Hardware
E105 – Invalid PROFILE section/key name
•
Check spelling of section and key name in PROFILE
command
E106 – Invalid PROFILE value
•
Check that value being set in PROFILE command is
valid
E107 – Counter is already used as a trigger
•
The specified counter is already used as a schedule
trigger and cannot be used again.
E109 – File IO error:
detailed description
•
An error occurred while reading or writing to a file on
one of the drives (A: or B:). The detailed description will
contain exact details of the error type. For example, a
write-protected file cannot be written to.
E110 – Error accessing storefile:
detailed
description
•
An error occurred while reading or writing to a storefile
containing logged data. The file may be corrupted.
E112 – Parameter/option conflict
•
The specified combination of command parameters or
channel options are not valid
E113 – Schedule option error
•
Invalid schedule option specified
E114 – Command parameter error
•
Invalid parameter specified for a command
E115 – Serial sensor control string error
•
Invalid syntax within serial sensor control string
E116 – Cannot log:
detailed description
•
The
DT80
cannot log data for one or more schedules
for the indicated reason
•
If the problem was that an existing job of the same
name had logged data/alarms then you need to give the
new job a different name, or delete the old job’s data
using DELDATA/DELALARMS
E117 – Incompatible schedule store units and
trigger
•
You can only specify storefile size by time (e.g. 12
hours data) if the schedule trigger is time based.
E118 – Error accessing drive
x
:
detailed
description
•
The indicated drive (A: or B:) could not be accessed
•
Media may be absent, not formatted or faulty.
E119 – No matching storefiles found
•
There are no storefiles for the specified job/schedule
E122 – Command incompatible with configured
port function
•
nSERIAL channel or trigger defined, or SSDIRECT
command used, and specified serial port has not been
configured as a serial channel in the profile
E123 – SSDIRECT mode already active
•
SSDIRECT command was issued but SSDIRECT mode
is already active on another comms port. Use
ENDSSDIRECT to cancel SSDIRECT mode.
E124 – Modbus transaction failed
•
could not establish connection to Modbus slave device,
or no response to request
E125 - Modbus - write attempt to read-only
register
•
Modbus discrete inputs and input registers (types 1 and
3) cannot be written to using an expression
E126 - Modbus not supported on this channel
•
Modbus channel should be 1,2,3 or 4