DT80 Range User Manual
Page 274
RG
Safe Mode
If there is an error in the
DT80
's profile settings or the job that is automatically loaded following hard reset then you may
find that you are unable to communicate with the logger. For example – the startup profile specifies the wrong RS232
parameters (and you're not sure what they are), or the job specifies an immediate
1SERIAL
channel with a very long
timeout (and the serial channel is not connected to anything).
Safe Mode
provides a mechanism to regain control and fix the problem. To select safe mode you need to perform a
"triple-push" reset:
1.
Press the manual reset button
2.
Wait approximately 3 seconds, then press the reset button again.
3.
Wait approximately 3 seconds, then press the reset button a third time.
4.
Verify that
DT80 restarted
/
Safe mode
is displayed on the LCD.
This will have the same effect as a
hard reset
, except that:
•
all profile settings are ignored – factory default settings are used (for example, the host port parameters will be
set to
57600,8,N,1,SWFC
)
•
no job is loaded
•
any queued unload or alarm messages will not be attempted
Note:
the profile settings are not cleared – they are simply ignored for this session only. If you now do a normal hard reset they will once
again be loaded.
Factory Settings
To restore the
DT80
to factory default settings, send the
FACTORYDEFAULTS
command, which will reset all profile
settings to their factory defaults, then perform a hard reset.
Note:
this command does not delete any files from the internal file system. The
DELALLJOBS
command may be used to remove all
jobs and all logged data.