Setting the operating
mode
Sequence of operations
•
: (
Outsi
de) The output gets switched on, when
the displayed physical value isn’t between the low limit
value (L.LI) and the high limit value (H.LI).
•
(
Warm
) The output gets switched on, when the
displayed physical value is lower than the low limit value
(L.LI), When the displayed current value is higher or equal
than L.LI, than the state of output doesn’t change.
The output gets switched off when the displayed physical
value is higher than the upper limit value (H.LI). When the
displayed physical value is lower or equal than H.LI, than
the state of limit output doesn’t change.
This operating mode is used in other DATCON instruments.
Here you can use it at any control task where the physical
value is the process value and you can control the process
through the limit outputs.
•
(
Cool
) The output gets switched on, when the
displayed physical value is higher than the high limit value
(H.LI). When the displayed physical value is lower or equal
than H.LI, than the state of limit output doesn’t change.
The output gets switched off when the displayed physical
value is lower than the lower limit value (L.LI). When the
displayed physical value is lower or equal than L.LI, than
the state of limit output doesn’t change.
This operating mode is used in other DATCON instruments.
Here you can use it at any control task where the
temperature is the process value and you can control the
process through the limit outputs.
•
: (
On
= switched on) The output is switched on
independently from the measured value.
Exit from the operating
mode menu item
6. After selecting the limit output mode press
MENU button
you will see:
.
7. If you had selected the
or the
mode, there is no
need to do any further settings. For finishing the operation,
please go on from the point
Exit from the menu item
.
Summary of Contents for DT1400 RL2 IA
Page 1: ...DT1400 xx xx Limit switch Operating Instructions ...
Page 68: ...DT1400 xx xx 68 20170920 V0 10 2 Application example Analog output option ...
Page 69: ...DT1400 xx xx 20170920 V0 69 RL4 option ...
Page 70: ...DT1400 xx xx 70 20170920 V0 TS option ...
Page 71: ...DT1400 xx xx 20170920 V0 71 ...
Page 72: ......