7.15. Analoge output signal setting
(16. menu item)
Function
In this menu item you can choose between 4-20 mA and
0-20 mA output current. [Factory default: 4-20 mA]
Sequence of operations
1. Enter the menu by typing a supervisor code.
The way the code should be type is described in Chapter
7.1. Typing the code in.
You see on the display:
.
2. Keep stepping by pressing the
▲
button as long as you
see this menu item:
(
Ana
log).
3. Enter the menu item by pressing the
ENTER
button.
4. You see this:
on the display The text is
blinking, signaling that it can be modify
5. Pressing
▲
button you can choose between the two
output signal:
•
: 4-20 mA current output [Factory default]
•
: 0-20 mA current output.
Exit from the menu item
1. After you have performed the setting, press the
MENU
button. This takes you out from the menu item, and you see
this:
.
(2. If you want to change the setting you have done just
now, or if you just want to check what you have typed in, go
on with the operation from point 3 of the
Sequence of
operations
.)
(3. If you do not want to exit from the menu because you
want to perform other settings too, you may press the
▲
button to select the desired menu item.)
Exit from the menu
Press the
MENU
button. First the mnemonic
(
Save
),
then the mnemonic
(
Exit
) are shown on the display.
With this the storing of the settings is completed. The
instrument has exited the menu and goes on with the
measurement
Summary of Contents for DT1400 RL2 IA
Page 1: ...DT1400 xx xx Limit switch Operating Instructions ...
Page 68: ...DT1400 xx xx 68 20170920 V0 10 2 Application example Analog output option ...
Page 69: ...DT1400 xx xx 20170920 V0 69 RL4 option ...
Page 70: ...DT1400 xx xx 70 20170920 V0 TS option ...
Page 71: ...DT1400 xx xx 20170920 V0 71 ...
Page 72: ......