DT1400 xx xx
66
20170920-V0
Limit outputs
Output type:
2 NO SPST relays
Contact rating:
30 VDC, 3 ADC / 240 VAC, 3 AAC
Refreshing time:
Equal dispaly refreh time
Limit outputs (optional)
Output type:
2 NO SPST relays
Contact rating:
30 VDC, 3 ADC / 240 VAC, 3 AAC
Refreshing time:
Equal dispaly refreh time
Active analog output (optional)
Output type:
galvanic isolated DC current
Output ranges:
4-20 mA / 0-20 mA (scalable)
Characteristic: Linear
Accuracy: 0.03%
@
Ta
=
23
˚
C ±2
˚
C,
(after 10 min warm up time)
Accuracy:
0.4 % @ -20°C < Ta < +60
˚
C
Temperature-dependency: 75
ppm
/
˚
C
Burden: max.
500
ohm
Overcurrent protection:
25 mA
Overvoltage protection:
75 V (normal polarity)
Reverse polarity: protected by 63 mA fuse
Isolation voltage:
0.5 kV
Passive analog output (optional)
Output type:
galvanic isolated DC current
Output ranges:
4-20 mA / 0-20 mA (scalable)
Characteristic: Linear
Accuracy: 0.03%
@
Ta
=
23
˚
C ±2
˚
C,
(after 10 min warm up time)
Accuracy:
0.4 % @ -20°C < Ta < +60
˚
C
Temperature-dependency:: 75
ppm
/
˚
C
Output supply voltage:
4 V - 30 V
Overcurrent protection:
25 mA
Overvoltage protection:
75 V
Maximum loop resistance:
R
max
= (U - 4 V) / 0.02 A [ohm]
(U voltage of external power supply)
Minimum loop resistance:
U < 20 V not required
U > 20 V R
min
= (U - 20 V) / 0.02 A [ohm]
(U voltage of external power supply)
Isolation voltage:
0.5 kV
Summary of Contents for DT1400 RL2 IA
Page 1: ...DT1400 xx xx Limit switch Operating Instructions ...
Page 68: ...DT1400 xx xx 68 20170920 V0 10 2 Application example Analog output option ...
Page 69: ...DT1400 xx xx 20170920 V0 69 RL4 option ...
Page 70: ...DT1400 xx xx 70 20170920 V0 TS option ...
Page 71: ...DT1400 xx xx 20170920 V0 71 ...
Page 72: ......