TECHNICAL NOTES

Ordering Information and Selection Guide

MPS Part No.  

Rated Power 

Efficiency 

~

 

V1 Output 

V2 Output 

V3 Output

DMS-PS1-CM

 

5  Watts 

75% 

5Vdc/1A 

 — 

 —

DMS-PS2-CM

 5 

Watts 

73% 

5Vdc/0.65A 

4.85Vdc/0.2A 

 

DMS-PS3-CM

 5 

Watts 

71% 

5Vdc/0.35A 

4.85Vdc/0.2A 

4.85Vdc/0.2A

DMS-PS4-CM

 

10  Watts 

80% 

24Vdc/0.45A 

 — 

 —

DMS-PS5-CM

 10 

Watts 

75% 

24Vdc/0.35A 

4.85Vdc/0.2A 

 

DMS-PS6-CM

 10 

Watts 

73% 

24Vdc/0.30A 

4.85Vdc/0.2A 

4.85Vdc/0.2A

DMS-PS7-CM

 

16  Watts 

82% 

24Vdc/0.70A 

 — 

 —

DMS-PS8-CM

 16 

Watts 

76% 

24Vdc/0.60A 

4.85Vdc/0.2A 

 

DMS-PS9-CM

 16 

Watts 

74% 

24Vdc/0.55A 

4.85Vdc/0.2A 

4.85Vdc/0.2A

DMS-PS10-CM

 

16  Watts 

82% 

12Vdc/1.35A 

 — 

 —

1. Shock Hazard:

 DMS-PS-CM Series power supplies feature touch-proof 

terminals blocks and fully-isolated plastic construction, thereby greatly reduc-
ing the risk of electrical shock. However, these are mains-powered devices 
whose operation is derived from hazardous and potentially lethal voltages. 

 

All service and installation must be performed by qualified personnel, with 
the ac supply voltage de-energized. Before making connections to  any of 
the unit’s terminal blocks, use a digital voltmeter to verify that the ac supply is 
de-energized (off).

2.  AC Supply Fuse (F1):

 All DMS-PS-CM Series power supplies are equipped 

with a built-in 1A/250V time-lag fuse. Replacement fuses must be of the 
same type and rating; please refer to the Functional Specifications section 
of this datasheet for more information. F1 is conservatively rated in order 
to reduce nuisance tripping which might occur during power-up or output 
overload conditions. However, F1 is primarily intended to provide protection in 
the event of catastrophic failure in the DMS-PS-CM’s ac/dc converter.

IMPORTANT! To ensure safe and reliable operation, DMS-PS-CM 
power supplies must be installed and serviced by qualified 
personnel. Contact Murata Power Solutions if there is any doubt 
regarding their installation and/or operation. Please read all of the 
following technical and application notes BEFORE installing or 
making connections to DMS-PS-CM power supplies.

3. Fuse Replacement:

 If any dc-output drops to zero volts, and no fault 

conditions exist within the external load circuitry or the ac mains, F1 may 
have failed. F1 is located on the circuit (etch) side of the pc-board. Fuse 
replacement is performed by first de-energizing and then disconnecting 
the ac mains from TB4. Next, disconnect all load wiring from TB1, TB2, 
and TB3. Lastly, remove the four screws that secure the pc-board to the 
plastic case. After making sure that the new fuse is securely attached to its 
mounting clips, re-assemble the unit using all four screws. Reconnect all 
input and output wiring and re-apply ac power.

 

If the unit still does not operate properly, and the ac supply at TB4 is 
measured to be within its specified operating range, the power supply 
is defective and must be replaced. Except for F1, DMS-PS-CM supplies 
contain no other user-serviceable components. 

4.  Wire Gauges and Fusing:

 All wiring connected to the DMS-PS-CM’s 

terminal blocks must meet the requirements specified in the Functional 
Specifications section. All ac supply and load wiring must be rated for the 
voltages and currents they will conduct and must comply with any code 
or application-mandated requirements pertaining to the user’s specific 
installation. Applications subject to vibration should include adequate strain 
reliefs on both input and output wiring. Install the strain reliefs within 2-3 
inches (5-7.5cm) of the terminal blocks.

 

It is recommended that all wiring be rated for 600V and 105°C operation 
(UL1015 type, for example). Also, wire insulation must be stripped to within 
±10% of the dimensions shown in Figure 2. All wires must be inserted 
into their respective terminal blocks such that the screw terminal does not 
pinch their insulation. 

No more than two wires should be connected to 

any single terminal on TB1 through TB4. 

If two wires are attached to a 

single terminal, be sure to use only two 20AWG (0.5mm

2

) wires on TB1, 

TB2, and TB3, and only two 18 or 20AWG (0.75 or 0.5mm

2

) wires on TB4.

Dangerous, potentially lethal voltages are present during normal 
operation. Disconnect ac mains before servicing. 
Reference document: IEC 417, No. 5036.

Caution, refer to accompanying documents for more informa-
tion. Reference document: ISO 3864, No. B.3.1.

Caution, unit may become hot in normal operation, thereby creat-
ing a potential burn hazard. Disconnect ac mains and then allow 
unit to cool before servicing.  
Reference document: IEC 417, No. 5041.

Figure 2. Insulation Strip Length

0.25"

(6.4mm)

Warnings

 (Marking)

~

Efficiency typical @120V/60Hz

DMS-PS-CM Series

High Efficiency, AC/DC Instrumentation Power  

Supplies with Individually Isolated Outputs

MPM_DMS-PS-CM.B02

 

Page 3 of 8

Technical enquiries

 email: sales@murata-ps.com, tel: 

+1 508 339 3000

www.murata-ps.com

Summary of Contents for DMS-PS-CM

Page 1: ...shock resistant terminal blocks for all I O connections Multiple outputs low noise low cost high efficiency double isolation and rugged construction combine to make DMS PSX CM Series AC DC power supplies the ideal choice for powering today s sensitive instrumentation and any electronic device that requires a reliable dc voltage Figure 1 DMS PS CM Series Simplified Schematic or 110 340Vdc TB4 F1 1A 2...

Page 2: ...Nm Rated Voltage 630V VDE 0110 V Group 2 250V VDE 0110 V Group 3 EMI All models Meets CISPR Pub 22 FCC Class B Safety Approvals Pending DC Outputs Line Regulation All outputs 0 1 max Load Regulation V1 All models 2 V2 V3 All models 0 2 max Output Accuracy Max V1 All models 2 0 V2 V3 All models 2 5 Hold UpTime 47 63Hz 115Vac 20mSec typ 230Vac 80mSec typ Noise Ripple All models 20MHz bandwidth See N...

Page 3: ...g and then disconnecting the ac mains from TB4 Next disconnect all load wiring from TB1 TB2 and TB3 Lastly remove the four screws that secure the pc board to the plastic case After making sure that the new fuse is securely attached to its mounting clips re assemble the unit using all four screws Reconnect all input and output wiring and re apply ac power If the unit still does not operate properly...

Page 4: ...ending on model 9 Temperature Derating See Figure 3 All DMS PS CM supplies are speci fied to operate at their full rated power over the temp range of 0 C to 50 C in still air convection cooling without any thermal derating For operation over 50 C in still air derate the output power linearly by 2 5 per C down to 50 rated power at 70 C To operate the units at full rated power between 50 C and 70 C a...

Page 5: ...regard to ground loop problems that may be encountered when powering 800 DPM s from a single power supply Application Information 1 Chassis Mounting Considerations In order to minimize self heating DMS PS CM power supplies should always be mounted in either a vertical or horizontal position Avoid mounting units upside down or in close proximity to other heat generating devices Also be sure to use ...

Page 6: ...MS PS6 CM V1 24V DMS PS9 CM V1 24V DMS PS3 CM V2 4 85V DMS PS6 CM V2 4 85V DMS PS9 CM V2 4 85V DMS PS CM Series High Efficiency AC DC Instrumentation Power Supplies with Individually Isolated Outputs MPM_DMS PS CM B02 Page 6 of 8 Technical enquiries email sales murata ps com tel 1 508 339 3000 www murata ps com ...

Page 7: ... CM V2 4 85V DMS PS9 CM V2 4 85V DMS PS3 CM V1 5V DMS PS6 CM V1 24V DMS PS9 CM V1 24V Typical Performance Curves TA 25 C VIN 120V 60Hz DMS PS CM Series High Efficiency AC DC Instrumentation Power Supplies with Individually Isolated Outputs MPM_DMS PS CM B02 Page 7 of 8 Technical enquiries email sales murata ps com tel 1 508 339 3000 www murata ps com ...

Page 8: ...use or sell equipment constructed in accordance therewith Specifications are subject to change without notice 2008 Murata Power Solutions Inc USA Mansfield MA Tel 508 339 3000 email sales murata ps com Canada Toronto Tel 866 740 1232 email toronto murata ps com UK Milton Keynes Tel 44 0 1908 615232 email mk murata ps com France Montigny Le Bretonneux Tel 33 0 1 34 60 01 01 email france murata ps com...

Reviews: