background image

Mechanical Dimensions: Inches (mm)  Tolerances: 2 PL DEC ±0.02 (±0.51), 3 PL DEC ±0.010 (±0.254)

Transient Response - 10% to 100% Load  Step 

DMS-PS3-CM V2 

(+4.85V)

DMS-PS6-CM V2 

(+4.85V)

DMS-PS9-CM V2 

(+4.85V)

DMS-PS3-CM 

V1 (+5V)

DMS-PS6-CM 

V1 (+24V)

DMS-PS9-CM 

V1 (+24V)

Typical Performance Curves  

  T

A

 = +25°C, V

IN

 = 120V @60Hz

DMS-PS-CM Series

High Efficiency, AC/DC Instrumentation Power  

Supplies with Individually Isolated Outputs

MPM_DMS-PS-CM.B02

 

Page 7 of 8

Technical enquiries

 email: sales@murata-ps.com, tel: 

+1 508 339 3000

www.murata-ps.com

Summary of Contents for DMS-PS-CM

Page 1: ...shock resistant terminal blocks for all I O connections Multiple outputs low noise low cost high efficiency double isolation and rugged construction combine to make DMS PSX CM Series AC DC power supplies the ideal choice for powering today s sensitive instrumentation and any electronic device that requires a reliable dc voltage Figure 1 DMS PS CM Series Simplified Schematic or 110 340Vdc TB4 F1 1A 2...

Page 2: ...Nm Rated Voltage 630V VDE 0110 V Group 2 250V VDE 0110 V Group 3 EMI All models Meets CISPR Pub 22 FCC Class B Safety Approvals Pending DC Outputs Line Regulation All outputs 0 1 max Load Regulation V1 All models 2 V2 V3 All models 0 2 max Output Accuracy Max V1 All models 2 0 V2 V3 All models 2 5 Hold UpTime 47 63Hz 115Vac 20mSec typ 230Vac 80mSec typ Noise Ripple All models 20MHz bandwidth See N...

Page 3: ...g and then disconnecting the ac mains from TB4 Next disconnect all load wiring from TB1 TB2 and TB3 Lastly remove the four screws that secure the pc board to the plastic case After making sure that the new fuse is securely attached to its mounting clips re assemble the unit using all four screws Reconnect all input and output wiring and re apply ac power If the unit still does not operate properly...

Page 4: ...ending on model 9 Temperature Derating See Figure 3 All DMS PS CM supplies are speci fied to operate at their full rated power over the temp range of 0 C to 50 C in still air convection cooling without any thermal derating For operation over 50 C in still air derate the output power linearly by 2 5 per C down to 50 rated power at 70 C To operate the units at full rated power between 50 C and 70 C a...

Page 5: ...regard to ground loop problems that may be encountered when powering 800 DPM s from a single power supply Application Information 1 Chassis Mounting Considerations In order to minimize self heating DMS PS CM power supplies should always be mounted in either a vertical or horizontal position Avoid mounting units upside down or in close proximity to other heat generating devices Also be sure to use ...

Page 6: ...MS PS6 CM V1 24V DMS PS9 CM V1 24V DMS PS3 CM V2 4 85V DMS PS6 CM V2 4 85V DMS PS9 CM V2 4 85V DMS PS CM Series High Efficiency AC DC Instrumentation Power Supplies with Individually Isolated Outputs MPM_DMS PS CM B02 Page 6 of 8 Technical enquiries email sales murata ps com tel 1 508 339 3000 www murata ps com ...

Page 7: ... CM V2 4 85V DMS PS9 CM V2 4 85V DMS PS3 CM V1 5V DMS PS6 CM V1 24V DMS PS9 CM V1 24V Typical Performance Curves TA 25 C VIN 120V 60Hz DMS PS CM Series High Efficiency AC DC Instrumentation Power Supplies with Individually Isolated Outputs MPM_DMS PS CM B02 Page 7 of 8 Technical enquiries email sales murata ps com tel 1 508 339 3000 www murata ps com ...

Page 8: ...use or sell equipment constructed in accordance therewith Specifications are subject to change without notice 2008 Murata Power Solutions Inc USA Mansfield MA Tel 508 339 3000 email sales murata ps com Canada Toronto Tel 866 740 1232 email toronto murata ps com UK Milton Keynes Tel 44 0 1908 615232 email mk murata ps com France Montigny Le Bretonneux Tel 33 0 1 34 60 01 01 email france murata ps com...

Reviews: