30
Stop P.
10Bar
Alarm and stop the machine when the air supply
temperature reaches this set value
Unload P. upper
limit
8Bar
The Unload Limit Pressure in the Customer
Parameter must be set lower than this value.
MODI LOAD
TIME
****Hours
The manufacturer can modify the load running
time
MODI TOTAL
TIME
****Hours
The manufacturer can modify the total running
time
History fault reset
****
Input the history failure password to clear all the
history failures.
Unbalance scope
0006
When (the max. phase current / min. phase
current) is greater than (1+set value), the
unbalance protection will stop the machine. If
the set value is greater than 15, the unbalance
protection will be unavailable.
Lack phase
protection
005.0S
Set the LACK PHASE TIME ≥20S, the Lack
phase protection will be disabled
PRODUCT DATE
****-**-**
The manufacturer input the product date of the
unit.
Operation
SERIAL NUMBER
********
The manufacturer input the product
No. of the unit
PHASE PROTECT
ON/OFF
ON:Select sequence protection
OFF:Not select sequence protection
SELECT FREQ
50H
Set the power frequency
SEQ MODE
COMPATIBLE/ADVANCED
HIGH VOLTAGE
****V
Controller detects the voltage higher
than the set value, the shutdown
protection, reported voltage is too
high. Set this value to 0000, the high
voltage function is no function