background image

 

Getting Started

Page 7

 

If you have a 

 

Health EnviroMonitor

 

, on the other hand, Davis does recom-

mend tilting the UV sensor. The Health’s temperature-humidity-sun-wind 
index calculations assume that the UV sensor is tilted according to your lati-
tude. Additionally, maximizing UV readings (via tilting) gives the best indi-
cation of potential health risk.

To maximize UV and/or solar radiation reception: 

a. Recalibrate the anemometer to point north in the Northern Hemisphere, 

south in the Southern Hemisphere (see “Recalibrating the Wind Vane” 
on page 12 for instructions). 

b. Position the EZ-Sensor Arm to point either east or west. 
c. Tilt the sensor(s) toward the sun (south in the Northern Hemisphere, 

north in the Southern Hemisphere). 

 

Note:

 

This alternative configuration is not standard for meteorological measurements. 

 

Use the following rubric to determine the tilt angle for maximum readings:

 

 

Maximum Readings During Spring or Fall

 

If you want maximum readings in the Spring or Fall, use your latitude as 
the angle (that is, at 45˚ latitude, use an angle of 45˚ from vertical).

 

 

Maximum Readings During Summer

 

If you want maximum readings in the Summer, subtract 18˚ from your 
latitude to determine the correct angle (that is, at 45˚ latitude, use an 
angle of 27˚ from vertical).

 

 

Maximum Readings During Winter

 

If you want to maximize readings in the Winter, add 18˚ to your latitude 
to determine the correct angle (that is, at 45˚ latitude, use an angle of 63˚ 
from vertical).

For greater accuracy in determining the correct angle, consult a table of the 
sun’s declination over the desired time span. The best tilt angle is derived by 
subtracting declination from latitude. 

Summary of Contents for Energy EnviroMonitor

Page 1: ...dard and industrial The industrial option offers greater protection from radio frequency interference electrostatic discharges and voltage surges by provid ing 100 feet of shielded cable an extra grou...

Page 2: ...ctor Cone EZ Sensor Arm Additional Components for INDUSTRIAL Installations Only ICAM Kit 8 Conductor Cable Standard for ICAM to Console 25 7 5m 16 5 5m Ground Wire 6x1 25mm Screws Cable Ties Adhesive...

Page 3: ...the extension tube page 4 Attach the anemometer page 4 Attach the wind cups page 4 Snip the cable tie in the rain collector page 5 Apply power to the console page 5 Attach the EZ Sensor Arm page 6 Con...

Page 4: ...s positioned over the white field case and NOT over the black rain collec tor cone 3 Attach the wind cups to the anemometer Push the wind cups onto the shaft as far as they will go then tighten the se...

Page 5: ...rge tab between the two oblong holes on the base s underside and pulling the base free Plug the power adapter into the center Power slot as shown below and then plug the other end into a 110 VAC outle...

Page 6: ...port tube insert the EZ Sensor Arm letting the wire drop through the bottom gap in the brace clamp and tighten Alternative EZ Sensor Arm Positioning You may face the sensors straight up as shown above...

Page 7: ...ere Note This alternative configuration is not standard for meteorological measurements Use the following rubric to determine the tilt angle for maximum readings Maximum Readings During Spring or Fall...

Page 8: ...d release the lever d Connect the bare drain wire to the SHIELD terminal JP2 and cut off any excess drain wire e Attach the ground wire to the SHIELD terminal JP2 as well Run the ground wire and the s...

Page 9: ...in the sensor array field case keeping in mind that you will need a power source you should locate the console indoors For more accurate readings follow these suggestions Avoid placing console in dir...

Page 10: ...the station facing a different direction see Recali brating the Wind Vane on page 12 for instructions on how to adjust the wind vane accord ingly Note For roof mounting we recommend the optional Mount...

Page 11: ...ble underneath the eaves of your house or in another location similarly shielded from rain place cable clips or weather resistant cable ties approximately every 3 5 feet 1 1 6 m Note Do not use metal...

Page 12: ...compass or local area map to determine which direction N S E W NE etc the anemometer arm is pointing 4 Use the wind direction chart to find the degree reading which corresponds to that direction 5 Sl...

Page 13: ...ON A SHELF Or to display the console on a wall follow these steps a Hold the mounting base flat against the wall and use a pencil to mark the location of the two keyholes b Use an electric drill with...

Page 14: ...AC DC power cord and listen for 2 beeps within 10 seconds Note If you have the WeatherLink installed listen for 3 beeps within 20 seconds and then if all is well try communicating with the WeatherLink...

Page 15: ...ly with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installati...

Page 16: ...iroMonitor and Health EnviroMonitor Systems Rev A Manual 7 8 99 Controlled online Weather Manuals Consoles EZ EZ Adv This product complies with the essential protection requirements of the EC EMC Dire...

Reviews: