background image

 

Page 8

Alarm Output Module

 

 

Latch Circuit Outputs (L1 and L2) and Red LED Indicators

 

The AOM includes two latch circuits; each has one output contact and a 
red LED indicator. The latches are set and reset by selected alarms, 
enabling the user to set up two simple control circuits in which each out-
put “contact” is set on by one alarm and set off by another. (For example, 
start a fan when the high temperature alarm becomes active and keep it 
running until the low temperature alarm becomes active.) The red LED 
indicators display the status of each of the latches. When the LED is 
lighted, the output is closed.

 

If using latch circuits, jumper J7 must be placed in the NORMALLY-
OPEN position.

 

 

Latch Circuit L1 is set 
on (output CLOSED) 
by alarm output A 
and reset by alarm 
output B.

 

 

Latch Circuit L2 is set 
on (output CLOSED) 
by alarm output C and 
reset by alarm 
output D.

 

 

“ENABLE” switch (in the upper right corner of the AOM board)

 

The ENABLE switch opens all outputs when set to “OFF”. The indica-
tors continue to display the condition of the selected alarms or remote 
control lines.

 

 

Power Connector (A2)

 

To provide power to the AOM, you must connect the AOM power 
adapter to connector A2.

 

 

AOM Cable Connector (A1)

 

To enable the console to update the status of the AOM outputs, you must 
run the AOM Cable from connector A1 on the AOM to connector S6 on 
the sensor interface module (SIM) or the interface cable adapter module 
(ICAM).

 

 

Alarm Signal Selection Panel (J3 and J5)

 

The row of pin jacks at J3 enables you to program specific alarms for 
each of the four alarm outputs. Each of the numbered pin jacks at J3 is 
assigned to an alarm on the station (see “Connecting alarm signals to 
alarm outputs” on page 9 for a list of the pin assignments for each sta-
tion). The four pin jacks next to the solid white rectangles provide loca-
tions to “park” unused jumper wires.

Terminal J5 contains four jumper wires, one for each alarm output (A, B, 
C, D).To connect an alarm signal to one of the alarm outputs, insert the 
desired jumper wire from J5 in the appropriate pin jack on J3.

Summary of Contents for Alarm Output Module

Page 1: ...onitor or the Heath EnviroMonitor The GroWeatherLink and Energy WeatherLink also allow you to control two alarm outputs manually by turning them on or off from the software though the software is not...

Page 2: ...1 25 mm long Self Threading Screws Four Adhesive Pads TOOL AND MATERIALS NEEDED You will need some of the following tools and materials Relays You may need to obtain your own relays in order to switc...

Page 3: ...ONS The AOM may be connected to either the sensor interface module or to the Interface Cable Adapter Module The two illustrations below show typical AOM installations AOM CONNECTED TO SENSOR INTERFACE...

Page 4: ...Remove the cover by pushing down on the tabs at the top until you can remove the tabs from the slots REMOVING THE COVER Reattach the cover as shown below Make sure the tabs on top of the cover snap b...

Page 5: ...at terminal strip J3 for selection as outputs Four of the 16 are jumper selected by the user to drive the photo coupled outputs and appear as contact closures A B C and D closure indicated by lighted...

Page 6: ...s are within specification to arcing and contact welding as are mechanical relays The Con trol Output and Status contacts are rated as follows ALARM SIGNAL PIN ASSIGNMENTS J3 ALARM OUTPUT J3 PIN GROWE...

Page 7: ...r of alarm data from the console to the output contacts LOAD pulse Green Status LED Indicator and Contact Output OK The green LED is lighted and the contact is closed to indicate that the fol lowing a...

Page 8: ...he ENABLE switch opens all outputs when set to OFF The indica tors continue to display the condition of the selected alarms or remote control lines Power Connector A2 To provide power to the AOM you m...

Page 9: ...ing the AOM to the System and Powering the AOM page 12 Mounting the AOM page 14 Programming the AOM Programming the AOM involves three main steps connecting alarm signals to alarm outputs selecting be...

Page 10: ...connected to that output is active If using either of the two latch circuit outputs you must select normally open operation To select normally open operation place the jumper plug over the two pins cl...

Page 11: ...of the pair in J4 To place wires into the cage clamp strip about 5 16 8 mm of the insulation off each wire in the cable Use a small screwdriver to push down on the lever next to the cage clamp insert...

Page 12: ...and Powering the AOM The AOM may be connected to either the sensor interface module SIM or the interface cable adapter module ICAM depending on your installation See Typical AOM Installations on page...

Page 13: ...Page 13 Powering the AOM You may use a separate AC power adapter for the AOM and the console or you may use the power Y cable as shown below to connect power to both the console and the AOM from a si...

Page 14: ...a wall or other vertical surface attach the base to the mounting surface using the 6 x 1 screws Use two screws as pictured below when attaching to a stud Use three screws as pictured below in any othe...

Page 15: ...Operation of the Alarm Output Module Page 15...

Page 16: ...Instruments Part Number 7395 085 Alarm Output Module Manual Rev B Manual 7 7 99 This product complies with the essential protection requirements of the EC EMC Directive 89 336 EC Davis Instruments Cor...

Reviews: