CAP10G-MN-EN-01 

OCT-2020

CAP10G is the industrial version of PulseCAP10, designed specifically for generator fuel monitoring applications. The

CAP10 has 240..33 ohms resistor output allowing direct connection to a generator controller. It is compatible with most

popular generator controllers on the market such as DEEPSEA, EMKO, DATAKOM, COM AP, MGS, SMART GEN,

WOODWARD, POWERCOMMAND ... CAP10G with high precision up to 0.5%. Measuring range from 100mm - 3500mm.

The sensor has CE EMC certification according to EN61236-1 standard.

The technicians who install sensor, must be graduated from college of mechanic or electric.

The mechanical installation staff (drill, cut, grind, etc.) must have skills in mechanical engineering.

The electrical installation staff (connect, etc.) must have skills in electrical engineering.

The technician must be trained before using.

CAP10G is intended to use with Diesel Oil, Vegetable Oil.

CAP10G must not be used with other flammable fluid such as Gasoline, Alcohol, Ethanol, Acetone, Toluene or

other solvents.

USER GUIDE FOR FUEL LEVEL
SENSOR RESISTIVE OUTPUT
CAP10G

This document is applied for the following products

1. Introduction

2. Notes

3. Safety

Summary of Contents for CAP10G

Page 1: ...ication according to EN61236 1 standard The technicians who install sensor must be graduated from college of mechanic or electric The mechanical installation staff drill cut grind etc must have skills...

Page 2: ...astic flange onto tank for all type of tanks and only using screws for the thick and hard ones Sensor length Standard 700mm 1000mm optional 1200 or 1500mm Cuttable down to 200mm Longer than 1500mm sug...

Page 3: ...ers In case of using stainless steel rivet 12 Twist drill 4 mm In case of using stainless steel rivet 04 Tube cutter 13 Electrical tape 05 Swivel Blade 14 Cutting pliers 06 Hacksaw 15 Phillips screwdr...

Page 4: ...tral hole After determining the center of the oil tank we clean the surface and use a 38 mm drill to make a hole on the oil tank Remove any burrs from the drilled hole by a file Before drilling it is...

Page 5: ...L Original length of the sensor H Height of the tank Example Sensor length is L 2000 H 1700 mm C 326 mm Cut the sensor pipe length of 326 mm 7 Calibration After cutting make sure the sensor tube is cl...

Page 6: ...over the sensor and then use plastic and then use plastic twister seal to lock the head seal and connector seal to protect the sensor Please follow the below steps Note Step 1 Remove the cover Step 2...

Page 7: ...fore installation to avoid confusing White PWR 8 50VDC Blue PWR OVDC Black Resistive Output 240 33 Ohm Recommend to use 24VDC power The signal cable from sensor should be protected by corrugated hose...

Page 8: ...s Solutions 1 No output Sensor s powering wire is damaged Check out on the sensor s powering wire Overpowering has burnt the signal cable and circuit board Send to manufacturer Being tampered Check th...

Page 9: ...efects from the manufacturer depending on the actual situation Daviteq will consider replacement or repairs Notes One way was shipping cost to the warranty centre shall be paid by Customers 1 The warr...