background image

Parameter Measurement

Acceleration RMS & Peak

Velocity RMS & Peak

Displacement RMS & Peak

Frequency & Temperature

Acceleration range and resolution

+/- 25G, 6.1 mg

Velocity range and resolution

0 .. 50 mm/s, 0.1mm/s

Displacement range and resolution

+/- 5000 um, 1 um

Frequency range and resolution

2 .. 10,000 Hz, 1 Hz

The Daviteq V1A Vibration Sensor is calibrated at the factory. It is recommended the customer to re-calibrate the
sensor every 12 months. Please 

contact us

 for calibration services.

The Daviteq V1A Vibration Sensor together with a wireless transmitter to be used in the following cases:

Measuring Single-axis vibration and/or surface temperature of Motor, Bearing, Pump, Fan, Gearbox, Rotary
machine/equipment, or any object that has a vibration from 8 to 11,000 Hz.

Figure 1. The V1A sensor is mounted on a motor case.

3. Calibration of the Daviteq V1A Vibration Sensor

Notes: 
* The calibration and configuration can only be done when the V1A sensor is used with a Wireless transmitter
like Sub-GHz (WS433-V1A) or LoRaWAN (WSLRW-V1A) or Sigfox (WSSFC-V1A).
* After that, use the 

offline tool

 or downlink to configure the A factor to the device.

4. Application notes for the Daviteq V1A Vibration
Sensor

5. Installation

5.1 Dimension Drawings

Summary of Contents for Lidar People Counter

Page 1: ...Daviteq AC 5A Current Transducer Measurement Principle Daviteq Ultrasonic Level Distance Measuring Technologies Daviteq ULA Ultrasonic Level Sensor for Trash bin Daviteq Air Gas Flow Measurement Techn...

Page 2: ...Daviteq Optical Sensing Technologies...

Page 3: ...t with two distinct fields of view FoV to alternatively get a ranging distance from them and consequently recognize the movements of a person Using this method the number of people occupying a meeting...

Page 4: ...e sensor working properly The reliability of the algorithm relies on the accuracy of the setup which detects the distance between the sensor and the floor This can be ensured only if nothing e g no ob...

Page 5: ...r facing down to the floor It can be used for the gate or walkway with dimensions as below Width is from 700 to 1500mm Height is from 2000 to 3500mm The sensor can count people passing thru the gate i...

Page 6: ...nsor with optical lense PIR sensor with lense These 02 parts need to be checked and cleaned periodically depending on the environment ATTENTION DO NOT INSTALL THE SENSOR OUTDOOR OR INDOORS WITH HIGH I...

Page 7: ...o distinguish between when people are present and when no one is standing under the sensor The laser sensor will measure the distance value from the sensor ceiling to the floor When there are people t...

Page 8: ...Daviteq Radar Sensing Technologies...

Page 9: ...Daviteq Gas Detection Technologies...

Page 10: ...16SS sintered filter for Indoor use buy the optional accessory rain guard for outdoor installation What is cross sensitivity The electrochemical sensor is normally affected by other gas It meant the s...

Page 11: ...over time For example the NH3 sensor current output will be reduced by about 5 of the signal per six months in clean air at 25 oC temperature The R_gain of the circuit also has a 0 1 or 0 05 tolerance...

Page 12: ...wer ON the device Place the device in a clean air environment the target value is nearly zero at a temperature from 20 30 oC in at least 60 minutes It is better to use the 99 99 Nitrogen gas as zero g...

Page 13: ...ased on basic linear formula y A x B Where A B is calibration coefficients x is the sensor process value example gas level in ppm read on reading device RAW_VALUE in the payload such as on application...

Page 14: ...3 concentration in the ambient air Air quality monitor H2S H2S gas monitor for the sewage treatment system H2S gas monitor for indoor air quality H2S gas monitor for basement floor H2S gas monitor for...

Page 15: ...may take up to 30 days to recover If the sensor cannot recover after 30 days please replace the new sensor module 2 The measured value is always zero or near zero 2 1 The sensor module was removed Pl...

Page 16: ...ration sensor Please follow the calibration procedure in section 3 above Approx 6 12 months Sensor replacement Replace the new sensor module after 02 years of operation please check the sensor specifi...

Page 17: ...reless delivers the proper output value Below are some configuration parameters that store in the flash memory of the wireless transmitter Description Unit Default Format Property Comment CONSTANT_A 1...

Page 18: ...ampling method Diffusion Sensor housing Rating SS316 SS304 housing with 316SS sintered filter for Indoor use buy the optional accessory rain guard for outdoor installation Exd approval for Zone 1 or Z...

Page 19: ...40 60 C C3H8 0 05 vol or 5 of readings whichever is greater within the range of 20 25 C 0 1 vol or 30 of readings whichever is greater at 100 kPa test 80 kPa 100 kPa 120 kPa 0 1 vol or 15 of readings...

Page 20: ...gas molecules at a particular wavelength causing vibration of the gas molecules NDIR Non Dispersive Infrared gas sensors detect a decrease in transmitted infrared light which is in proportion to the...

Page 21: ...f molecular vibration The relationship between infrared transmittance and gas concentration is expressed by the Lambert Beer law Where is transmittance is the intensity of light passed through sample...

Page 22: ...ce the device in a clean air environment the target value is nearly zero at a temperature from 20 30 oC in at least 60 minutes After 60 minutes force the device to send data read and record the Raw_va...

Page 23: ...r process value example gas level in ppm read on reading device such as on application server network server on offline tool The process value is the RAW_VALUE in the payload y is the correct value y...

Page 24: ...cautions when operating electrical equipment intended for use in explosive areas in due course When dealing with a cylinder containing a gas mixture under pressure it is necessary to follow safety reg...

Page 25: ...ment What How When Cleaning the Filter Check and clean the filter every few months depending on the environment Clean the filter with warm water and soap then use compressed air to purge it from the i...

Page 26: ...output value Below are some configuration parameters that store in the flash memory of the wireless transmitter Description Unit Default Format Property Comment CONSTANT_A 1 Float R W Constant a for s...

Page 27: ......

Page 28: ...the same value for all sensors after manufacturing The sensor current output of a sensor will be changed over time For example the NH3 sensor current output will be reduced by about 5 of the signal pe...

Page 29: ...on cap as above pictures to attach to the sensor and connect the tubing to the gas cylinder Open the valve on the Cylinder slowly and make sure the gas has reached the sensor Please use the Flow regul...

Page 30: ...cture Because the Output is 0 10VDC we do recommend to use the following cable for extention Cable size minimum 24AWG or minimum 0 5 mm2 core Cable type Shielded Max recommended cable legnth 20m Note...

Page 31: ...Connect the wires to Reading device as below PWR 12 36VDC PWR GND OUT 0 10VDC OUTPUT NC Not used Plug the M12 connector to sensor Firmly tighten the M12 connection...

Page 32: ...2 The sensor is at the end of its life Replace the sensor module 3 The voltage output is 0V or random noise 3 1 The wiring problem Check the wiring and connector M12 Check power supply 3 2 The sensor...

Page 33: ...Approx 1 2 years Sensor replacement instructions Step 1 Remove the Protector by Rotate it anti clockwise Step 2 Unplug the sensor module Step 3 Remove the spring clip on the new sensor module Step 4 P...

Page 34: ......

Page 35: ...c m bi n u c gi tr kh ng ng nh t sau khi s n xu t T n hi u d ng i n ra c a c m bi n s thay i theo th i gian V d d ng i n u ra c a c m bi n NH3 s gi m kho ng 5 m i s u th ng trong kh ng kh s ch nhi t 2...

Page 36: ...n i ng v i b nh ch a kh M van tr n b nh kh t t v m b o kh c l u th ng n c m bi n Vui l ng s d ng van i u p 0 25 LPM ho c 0 5 LPM B t u b m gi nh d u m c th i gian Sau 2 ph t ghi nh n i n p ra sau ghi...

Page 37: ...u c Code A 4 l i nh h nh d i V thi t b xu t t n hi u 0 10VDC n n khuy n c o n n s d ng d y c p m r ng v i c i m sau Lo i d y c b c ch ng nhi u t i thi u 24AWG ho c l i t i thi u 0 5 mm2 Chi u d i d y...

Page 38: ...C m u n i M12 v o c m bi n Si t ch t k t n i M12...

Page 39: ...tra l i k t n i M un c m bi n v i bo m ch 2 2 C m bi n b h h ng Thay M un c m bi n 3 i n p ra lu n b ng 0 ho c b nhi u 3 1 L i u d y Ki m tra l i d y u n i v c p M12 Ki m tra l i ngu n c p 3 2 L i thi...

Page 40: ...kh l u th ng d d ng v o module c m bi n b n trong gi p c m bi n o ch nh x c Vui l ng xem h ng d n b n d i Sau kho ng 3 6 th ng Quy tr nh thay th m un c m bi n B c 1 Th o t m b o v b ng c ch v n ph n v...

Page 41: ...h nh x c kh ng kh m i tr ng xung quanh B c 1 Th o v b o v b ng c ch v n ph n v ng c chi u kim ng h B c 2 D ng bao nylong v d y thun d y chun b c l i m un c m bi n ch ng n c v h i m th m nh p v o u c m...

Page 42: ...B c 3 V sinh ph n v b o v b ng n c v kh n n m b o v b o v kh r o ho n to n sau khi v sinh B c 4 Th o bao nylon v l p l i v b o v b ng c ch v n theo chi u kim ng h END...

Page 43: ...Daviteq Electrical Sensing Technologies...

Page 44: ...eless transmitter of Daviteq It can connect to any brand of CT on the market The AC current from CT will go thru a precision resistor to convert to voltage value in mV then the electronics circuit wil...

Page 45: ...The Daviteq AC current transducer can connect to any Wireless transmitters manufactured by Daviteq which support DULP output DULP Digital Ultra low Power...

Page 46: ...the CT ratio in the wireless transmitter part The Daviteq AC current transducer is designed and manufactured with accuracy The user can do re calibrating the transducer by using an AC current calibrat...

Page 47: ...e threshold for protection for safety From the current load the sensor can count the run time of the machine equipment to deliver output how many hours of run and how many hours of OFF by setting the...

Page 48: ...Connect the AC transducer to the wireless transmitter via the M12 connector Make sure the connection is firm and tight as in below photo 5 2 Connect the AC transducer to Wireless Transmitter...

Page 49: ...ation of CT in the wireless transmitter again 2 2 Loosed connection of M12 connector of the transducer and wireless transmitter Check whether the M12 connector is firmly connected 2 3 Wrong A and B va...

Page 50: ...me configuration parameters that store in the flash memory of the wireless transmitter Description Unit Default Format Property Comment CONSTANT_A 1 Float R W Constant a for scaling measured value CON...

Page 51: ...Daviteq Ultrasonic Level Distance Measuring Technologies...

Page 52: ...re the time difference between the sound wave from the transmitting transducer and the receiving reflected sound wave From that it calculates the distance by the following formula D Time x V 2 Where D...

Page 53: ...25 80 oC 0 99 RH non condensing Accuracy at 25 oC 65 RH 1 cm 0 5 of reading value Transducer material Ceramic Rating IP68 1m of water depth in 1h The Daviteq ULA ultrasonic level sensor measures the...

Page 54: ...h bin or actual measurement Method 2 Read the sensor s measurement value when the trash bin is empty L0 Then H L0 How to determine the new coefficients A and B The calibration formula is L a x D b Cal...

Page 55: ...es Clean the transducer surface with a soft detergent and clean water 2 The distance value always shows 450 500 cm 2 1 The object is too far away from the sensor it is out of the detection range of th...

Page 56: ...d to do maintenance However depending on the installation environment the transducer must be checked and cleaned periodically for accurate measurement This ULA Ultrasonic level sensor has the default...

Page 57: ...Thermal mass flow Pitot tube Orifice plate Daviteq Air Gas Flow Measurement Technologies...

Page 58: ...1 There are 2 openings in the tubes one opening faces the flow directly to sense the stagnation pressure and the other is perpendicular to the flow to measure the static pressure Figure 1 Schematic of...

Page 59: ...ith the Air please configure the Density of Fluid kg m3 of the gas in the device Please refer to the memory map in this link The Daviteq AFD Air Gas Flow Sensor together with a wireless transmitter to...

Page 60: ...ndensation inside the sensor for accurate and reliable measurement Figure 3 Mounting direction of AFD flow sensor 5 1 Mounting Direction Notes The Arrow on the probe must be in the same direction of f...

Page 61: ...es will cause errors in flow measurement Figure 6 Maximum misalignment To ensure a homogeneous flow profile it is necessary to mount the AFD flow sensor at a sufficient distance to narrow or bend of t...

Page 62: ...specification of the flow sensor and wireless transmitter to ensure the complete set of devices is suitable for the process and environment of the installation Follow these steps Attach the nozzle wi...

Page 63: ...Insert the probe into the flange neck and tighten the locking screw Figure 10 Install the probe into the rectangular duct Figure 11 The probe is completely installed on the rectangular duct Unscrew t...

Page 64: ...Figure 12 Adjust the orientation of the probe 5 7 Attach the Wireless Transmitter to the probe...

Page 65: ...evice vibrates during operation 2 1 Forget to tighten the screws during installation Recheck the installation 3 There is leakage of Air Gas nearby the installation 3 1 The leakage could be from the O...

Page 66: ...on parameters that store in the flash memory of the wireless transmitter Description Unit Default Format Property Comment CONSTANT_A 1 Float R W Constant a for scaling pressure value in Pa CONSTANT_B...

Page 67: ...Daviteq Inertial Measurement Technologies...

Page 68: ...connection can be via a 2m cable with an M12 connector or integrated type WS433 only The V1A is also powered by the batteries in the wireless transmitter V1A utilizes the single axis Piezo accelerati...

Page 69: ...or together with a wireless transmitter to be used in the following cases Measuring Single axis vibration and or surface temperature of Motor Bearing Pump Fan Gearbox Rotary machine equipment or any o...

Page 70: ...surface temperature Here are some recommendations for the installation of V1A on some typical equipment based on standard ISO 20816 or ISO 10816 Figure 4 Measuring points for pedestal bearings Figure...

Page 71: ...is an M6 screw that comes with the sensor as standard There are 02 cases of mounting The V1A can be installed directly on the equipment s surface via an M6 screw or an adapter if the threads on the e...

Page 72: ...below figure Figure 12 Drilling and tapping an inner threads M6 on motor casing if the drilling is NOT allowed you can use the adhesive base Item code ACC V1A BASE 01 for mounting the V1A on the equi...

Page 73: ...l Apply the 2 part putty epoxy on the bottom surface of the base Place the base on the surface Use the leveling meter to level the surface of the base in 02 directions X and Y LEAVE IT COMPLETELY DRY...

Page 74: ...atus and replace it when necessary 2 The measured values are not as expected 2 1 The installation is not correct or not suitable for the sensor design Please recheck the installation 2 2 The sensor is...

Page 75: ...ge the configuration on the wireless transmitter so that the complete sensor sensor wireless delivers the proper output values Below are some configuration parameters that store in the flash memory of...

Page 76: ...d by the batteries in the wireless transmitter AG utilizes the three axis high accuracy MEMS acceleration sensor to calculate the static Euler angles of the object it is mounted on The microprocessor...

Page 77: ...nearity 0 0622 o Total error in 20 oC deviation 0 075 o Parameter Measurement X tilt angle Y tilt angle Z tilt angle The Daviteq AG Tilt Sensor is calibrated at the factory We highly recommend custome...

Page 78: ...ion direction is not correct Please recheck the installation 2 2 The sensor is drifting Please consult the manufacturer for a warranty or replacement 3 The reading values are very noisy even though th...

Page 79: ...There is no configuration required for the AG tilt sensor There is only configuration for the Wireless transmitter please refer to the wireless transmitter s manual END 8 Default configuration...

Page 80: ...Daviteq Pressure Measurement Technologies...

Page 81: ...tra low Pressure Sensor Gas Flow Instrumentation Air Flow Measurement HVAC VAV Pressure Monitoring Negative Pressure Room Monitor Positive Pressure Room Monitor Filter Clogging Monitor Safety Cabinets...

Page 82: ...6mm OD plastic tubes to connect to the H and L pressure ports of the sensor The mounting position must be chosen such that access to the Device is always possible Please take note of the specification...

Page 83: ...to do maintenance However the pressure sensor will drift over time We do recommend customer to re calibrate it every 12 months This ULP Sensor has the default configuration The user can change the co...

Page 84: ...e Measurement Technologies DEC 2022 Instructions for Grounding of Pressure Sensor CONNECTING GND FOR SENSOR Step 1 Open the blue housing of the sensor Step 2 Locate the GND point on the PCB same GND p...

Page 85: ...Step 3 Solder a wire to this GND point the other end of the wire will be screwed to 1 of 2 screws on the aluminum base...

Page 86: ...i Minh City Vietnam Step 4 Outside of the aluminum base there is another screw make a wire connection from this screw to the body of pressure sensor stainless steel cylindrical body Use a hose clamp o...

Page 87: ...Tel 84 28 6268 2523 4 ext 122 Email info daviteq com www daviteq com...

Page 88: ...Daviteq Soil Measurement Sensors...

Page 89: ...eps fast measurement no reagents unlimited detection times It can also be used for the conductivity of water and fertilizer integrated solutions and other nutrient solutions and substrates The electro...

Page 90: ...ency is detected by the frequency sweep circuit The dielectric constant of the soil can be measured so that the soil water content is obtained The dielectric constant of water is 80 F m 1 and the soil...

Page 91: ...e sensor please pay attention to shading and protection when using it in the field Clean the soil surface by removing the debris and vegetation Insert the electrodes completely in the soil as in the b...

Page 92: ...the manufacturer for a warranty or replacement 2 The measured values of EC Salinity and NPK are always zero or near zero 2 1 The soil moisture is too low less than 20 Therefore the circuit cannot mea...

Page 93: ...ation on the wireless transmitter so that the complete sensor transducer wireless delivers the proper output value Below are some configuration parameters that store in the flash memory of the wireles...

Reviews: