To understand how the AC current transducer can measure AC current, please refer to
for a complete
understanding of this measuring technique.
Below are some important configuration parameters which affect the operation of the device like battery life,
measurement accuracy, and alert threshold.
For Battery life estimation, please refer to this link.
measure_period | Default = 600s
This is the time period for the wireless transmitter to wake up and take the measurement from the transducer.
The default value is 600s. Users can reduce this value, but smaller value, shorter battery life!
cyclic_data_period | Default = 600s
Interval time to send an uplink message regardless of any conditions
sensor_boot_time | Default = 1000mS
This value will affect the measurement accuracy.
DO NOT change this value!
Those configuration parameters can be changed by downlink or offline tools. For more other configuration parameters,
please refer to the next section.
Sensor configuration can be configured in 02 methods:
Method 1: Configuring via Downlink message. Please find the instructions in
, but please take note of
the
FW version of the Document.
.
Some parameters are read-only, and some are read and writeable.
To read the parameters, use the off-line cable as above instruction.
Via uplink message, users can read only one parameter, which is the CURRENT_CONFIGURATION.
Below tables are the lists of the parameters of the device.
Read-only Parameter Table
Modbus
Register
(Decimal)
Modbus
Register
(Hex)
Function
Code
(Read)
No. of
Registers
Description
Range
Format
Property
Comment
2
2
3
4
FW_VERSION
string
Read
6
6
3
2
HW_VERSION
string
Read
8
8
3
2
DEVICE_ID
hex
Read
Product ID
10
A
3
4
DEVICE_PAC
hex
Read
Product PAC
14
E
3
1
SENSOR_TYPE
1-255
uint16
Read
Sensor or Input
Type
Read/Write Parameter Table
3.1.2 Operating principle of AC current transducer
3.1.3 Some important configuration parameters
3.2 Sensor Configuration
3.2.1 How to configure the Sigfox-Ready AC Current Sensor?
Note: THE SENSOR IS ONLY ACTIVE FOR OFFLINE CONFIGURATION IN THE FIRST 60 SINCE POWER UP
BY BATTERY OR PLUGGING THE CONFIGURATION CABLE.
3.2.2 What parameters of the device are configured?