Summary of Contents for SF

Page 1: ...SF WATER SOFTENER Installation Operating Manual...

Page 2: ......

Page 3: ...llation by bypass 4 2 4 Drain Line Connection 5 2 5 Brine Tank Re ll 5 3 1 Service 5 3 3 Brine Draw 6 3 2 Backwash 6 3 4 Slow Rinse 6 3 5 Rapid Rinse 6 3 6 Brine Tank Re ll 6 3 7 Control Valve Timer S...

Page 4: ...onal applications Particular features include 3 An extended model range with capacities from 1 to 20m hr with higher capacities being available using paired units Technology leading electronic control...

Page 5: ...an SF600 unit is as follows Exchange Capacity If resin capacity is 75gms CaCO litre and resin 3 volume 350litres 75x350 26 250gms CaCO3 Softening Capacity Assume water hardness 300ppm CaCO 3 3 26 250...

Page 6: ...Service Flow Brine Tank Volume Valve Tank Dimensions mm SF 200H SF 240H SF 300 SF 400H SF 500H SF 600 SF 900 SF 900H Outlet Sizes Weights kg 18 1 350 14 7 5 3 3 Autotrol 368 Autotrol 368 Autotrol 255...

Page 7: ...ick up the lead from the pipes which is a serious health concern WARNING Ensure installation is done in the right direction with the Flow IN and Flow OUT directions 2 2 Installation of a by pass It is...

Page 8: ...egenerate automatically preferably at night at 1am to 3am If power is disconnected the system could regenerate at a time when soft water is required Therefore always regenerate manually if water consu...

Page 9: ...ow Rinse At the end of the brine draw water is passed through the resin to replace the brine and rinse it out into the drain 3 5 Rapid Rinse The rinsing flow rate is increased to eliminate any lingeri...

Page 10: ...back washing Adequate back washing is essential to keep the bed of the unit clean for adequate regeneration 4 2 Cleaning of Softener Brine Tank Usually it is not necessary to clean out a brine tank u...

Page 11: ...Leak at distributor tube Make sure distributor tube is not cracked Check o ring and tube pilot Internal valve leak Replace seals and spacers and or piston 4 4 Maintenance Checks Daily Check the operat...

Page 12: ...Loss of mineral through drain line Loss of mineral through drain line Loss of mineral through drain line Fouled mineral bed Check backwash brine draw and brine tank fill Increase frequency of regener...

Page 13: ...Control cycles continuously Softener fails to draw brine Drain line flow control plugged Injector is blocked Injector screen is plugged Clean injector and replace screen Clean injector Clean screen L...

Page 14: ...des defects caused by fair wear and tear the effects of careless handling lack of maintenance faulty installation incompetence on the part of the equipment user Acts of God or any other cause beyond t...

Page 15: ...13...

Page 16: ...INS464A 09 20...