EtherSeries EMB-02 User’s Guide
44
Verify Proper Operation
Once the gateway is installed on your Network, verify proper
operation by testing its functionality. SCADA networks vary
greatly, so there is no simple way to describe testing all
possibilities. Use a scientific method and keep careful records
of all installation and troubleshooting steps. For example,
consider the following method…
1.
Verify that the gateway has a proper LAN connection by
pinging it. If it responds to a ping then…
2.
Verify the unit’s configuration by using telnet to port 8000
or by checking it using a web browser. If it looks good
then…
3.
Attempt a poll from the Modbus polling master computer.
If that works correctly, you’re ready to continue with
Modbus operation. IF not…
4.
Check the gateway’s statistics to see if it received the LAN
activity and passed the polls to a serial port. If not, there is
likely a problem with IP addressing or the host computer is
not configured correctly for the gateway’s LAN. If the
gateway receives the LAN packets and doesn’t pass them
to the serial port, then check its configuration. If the
counters indicate that the poll was passed to the serial port,
but there’s no response…
5.
Verify correct RS-232/RS-485 jumpers and configuration.
Verify cabling to the RTU. One of these is likely incorrect.
Or…
6.
Verify the RTU configuration. Perhaps it’s not correctly
configured.
Summary of Contents for EMB-02
Page 1: ...Revised March 25 2004 Firmware Version 1 4 EtherSeries Modbus Gateway EMB 2 User s Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 16: ......
Page 30: ...EtherSeries EMB 02 User s Guide 22 ...
Page 53: ...Troubleshooting 45 ...
Page 54: ......
Page 58: ...EtherSeries EMB 02 User s Guide 50 Ring Indicator Not used ...