background image

13

Each valve and air shutter is individually tested and adjusted prior to shipment. Normally adjustment is not required, however, vibration during 
transit, gas conversion or variations in the local gas supply may make minor adjustments necessary.

Check for the proper burner flame characteristics and adjust air shutters if necessary.  
Burner flames should be blue and stable with no yellow tips, excessive noise or lifting of the flame from the burner. If any of these conditions 
exist, check that the air shutter or burner ports are not blocked. If this condition persists, adjust the air shutter as required. If the flame is too 
yellow, indicating insufficient air, open the shutter to increase air inlet. If the flame is noisy or tends to lift away from the burner, indicating too 
much air, close the shutter to reduce air.  

IMPORTANT!

For warranty coverage, DCS requires that all burner adjustments be made by a qualified technician at the time of installation.  

IMPROPER ADJUSTMENT WILL VOID YOUR WARRANTY.

!3

   GRILL AND GRIDDLE BURNERS (SOME MODELS ONLY) 

Cooktop burners

To check that the ignition system operates correctly, light each burner  
by itself, then all burners in combination.

Check for a well-defined blue flame without any yellow tipping.

If any abnormality is evident, check that the components of the  
burner assembly are located properly.

When installing the burner port ring, align the two locating pins in the 
bottom side of the port ring with the locating notch and center holes on 
the top side of the simmer ring, and make sure these are properly engaged. 
Important! Incorrect installation may produce a potentially dangerous flame 
and result in poor burner performance.

No air shutter adjustment is possible on the cooktop burners. Proper 
operation is achieved with factory installed settings for the correct gas type.

If proper operation cannot be obtained, contact Customer Care or your 
nearest DCS by F&P Authorized Service Center.

The cooktop must not be used by the customer until proper operation has 
been achieved.

Air shutter

!1

   LEAK TESTING 

!2

   COOKTOP BURNERS 

 GAS 

ON 

GAS

ON

1

2

Fibre washer

Floating nut

Elbow (½” BSP external thread)

Foam Tape

Adhesive side

20 mm

50 mm

+50 mm

NG

ALL Models

Make sure the connection point will be accessible with the cooktop installed.

To enable the gas supply to be readily shut off by the customer, make sure the connection

is fitted with an isolating valve close to the cooktop.

Make sure to fit the supplied 

washer and regulator.

Adjust to obtain a 

test point

pressure of 1 kPa

 with the two 

semi-rapid burners operating at 

highest setting.

Ensure the hose is long enough to allow for removal of cooktop for servicing.

Make sure the connector is located as shown in step 5 CLEARANCE DIMENSIONS.

The hose assembly must be AS/NZS 1869 Class B or D certified, with an Rp ½” (ISO 7‐1) female thread connection.

The hose assembly must be as short as practicable and comply with relevant AS 5601/NZS 5261 requirements.

The hose must not be kinked, subjected to abrasion or permanently deformed.

The hose must not be near or in contact with any hot surfaces 

(e.g. base of metal hotlplate, flue, or chassis of underbench oven etc.)

If connecting the gas with a flexible hose:

LPG

recessed to 50 mm 

check all connections 

Make sure to fit the supplied 

washer and test point adaptor.

Make sure the 

supply pressure 

is regulated to 2.75 kPa

, with

the two semi-rapid burners 

operating at highest setting.

Washer

Washer

If converting to LPG, see 16 'Converting to a different gas type'

To check that the ignition system operates correctly, light each burner by itself, then all burners in combination.

Check for a well‐defined blue flame without any yellow tipping.

If any abnormality is evident, check that the components of the burner assembly are located properly

If proper operation cannot be obtained, contact your nearest F&P Authorised Service Centre. 

The cooktop must not be used by the customer until proper operation has been achieved.

yellow tip

lifting off

good flame

Arrow

Lifting off

Yellow tip

Good flame

After final gas connection is made, turn gas supply on and test all connections in gas 
supply piping for gas leaks with a soapy water solution. 

In order to avoid property damage or serious personal injury, never use a Iighted 
match or open flame.  
If a leak is present, tighten joint or unscrew, apply more joint compound, tighten 
again and retest connection for leak.

Summary of Contents for CPV2 SERIES

Page 1: ...Professional cooktop CPV2 models US CA INSTALLATION INSTRUCTIONS 591105A 04 16 www dcsappliances com ...

Page 2: ...to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in this manua...

Page 3: ...eliminate risk of burns or fire by reaching over heated surface units cabinet storage located above the surface units should be avoided California Proposition 65 The burning of gas cooking fuel generates some by products which are known by the State of California to cause cancer or reproductive harm California law requires businesses to warn customers of potential exposure to such substances To mi...

Page 4: ...e DO NOT discard any packing material box pallet straps until the unit has been inspected Remove the outer carton and any packing material from the shipping base The cooktop should be moved close to its final location Electric and gas connections should be made and the backguard installed before the cooktop is placed in its final position 48 models 36 models 30 models CPV2 488 CPV2 485GD CPV2 304 ...

Page 5: ...R ORIFICE MM NOMINAL RATING BTU HR C BURNER D BURNER D POWER BURNER NG LP NG LP NG LP CPV2 488 1 90 18 500 1 00 13 000 1 90 18 500 1 10 15 000 2 20 23 500 1 24 19 000 CPV2 486GD 1 90 18 500 1 00 13 000 1 90 18 500 1 10 15 000 2 20 23 500 1 24 19 000 CPV2 486GL 1 90 18 500 1 00 13 000 1 90 18 500 1 10 15 000 2 20 23 500 1 24 19 000 CPV2 485GD 1 90 18 500 0 95 11 500 1 90 18 500 1 10 15 000 2 20 23 ...

Page 6: ...cooktop 29 7 8 759 35 7 8 911 47 7 8 1216 D Overall depth of cooktop 28 1 8 714 28 1 8 714 28 1 8 714 E Height above countertop to top of grates 1 15 16 50 1 15 16 50 1 15 16 50 F Height from countertop to chassis top surface 3 8 10 3 8 10 3 8 10 G Height of chassis 8 3 8 213 8 3 8 213 8 3 8 213 H Distance from left edge of chassis to center line of gas inlet 2 1 2 63 2 1 2 63 3 77 I Distance from...

Page 7: ...of overhead cabinetry 13 330 13 330 13 330 F Width of cabinetry opening 30 762 36 914 48 1219 G Minimum clearance from from rear edge of cooktop to nearest combustible surface nearest non combustible surface 6 152 0 0 6 152 0 0 6 152 0 0 H Maximum depth from wall to cabinetry face projecting control panel flush control panel 24 3 16 614 26 5 8 677 24 3 16 614 26 5 8 677 24 3 16 614 26 5 8 677 Non ...

Page 8: ...TALLATION NO BACKGUARD USED NO BACKGUARD USED scenario 1 scenario 6 scenario 7 scenario 3 scenario 4 WALL MOUNT LOW BACKGUARD purchased separately WALL MOUNT HIGH BACKGUARD LOW SHELF purchased separately scenario 5 WALL MOUNT HIGH BACKGUARD HIGH SHELF purchased separately NO BACKGUARD USED Non combustible surface required Non combustible surface required Non combustible surface or Combustible surf...

Page 9: ...Mount High Backguard High Shelf scenario 5 opposite The cooking surface must sit flush or above the adjacent countertop level Note Backguard Installation Instructions can also be downloaded from our website www dcsappliances com Non combustible surfaces as defined in National Fuel Gas Code ANSI Z223 1 Current Edition Clearances from non combustible materials are not part of the ANSI Z21 1 scope an...

Page 10: ...m ventilation is not required Normally the maximum blower speed is only required when using the grill For best smoke elimination the lower edge of the hood should be installed a minimum of 30 762mm to a maximum of 36 914mm above the cooking surface If the hood contains any combustible materials e g a wood covering it must be a minimum of 36 914mm above the cooking surface Due to a high volume of v...

Page 11: ...maximum current draw of the model as detailed in the table below Please verify your model s current draw by checking the rating label on the cooktop Required grounding method This appliance is factory equipped with a power supply cord with a three prong grounding plug with polarized parallel blades It must be plugged into a mating grounding type receptacle connected to a correctly polarized 120 Vo...

Page 12: ...ance must be installed by a licensed plumber or gas fitter when within the Commonwealth of Massachusetts IMPORTANT DCS by Fisher Paykel recommends installing the manual shutoff valve in a location readily accessible by the customer so that gas to the appliance can be shut off in an emergency situation However the appliance must not be modified in any way to accommodate such placement Pipe sealant ...

Page 13: ...re properly engaged Important Incorrect installation may produce a potentially dangerous flame and result in poor burner performance No air shutter adjustment is possible on the cooktop burners Proper operation is achieved with factory installed settings for the correct gas type If proper operation cannot be obtained contact Customer Care or your nearest DCS by F P Authorized Service Center The co...

Page 14: ... in place ELECTRICAL Receptacle with properly rated over current protection is provided for service cord connection Adequate ground connection GAS SUPPLY Connection 1 2 NPT with a minimum 5 8 diameter flex line Site gas supply is compatible with cooktop model and sufficient pressure is available see section Gas connection The pressure regulator which is connected to the manifold is set for 5 0 W C...

Page 15: ......

Page 16: ...Surface de cuisson professionnelle Modèles CPV2 US CA INSTRUCTIONS D INSTALLATION 591105A 04 16 www dcsappliances com ...

Page 17: ...ur électrique N utilisez aucun téléphone dans l édifice Appelez immédiatement votre fournisseur de gaz en utilisant le téléphone d un voisin Suivez les consignes du fournisseur de gaz S il vous est impossible de joindre votre fournisseur de gaz appelez le service d incendie L installation et l entretien doivent être effectués par un installateur qualifié un centre d entretien ou le fournisseur de ...

Page 18: ...ce Proposition 65 de la Californie La combustion de combustibles de cuisson génère des sous produits qui sont reconnus par l État de Californie comme étant cancérigènes ou sources d anomalies congénitales Les lois de Californie exigent que les entreprises avertissent les clients de l exposition potentielle à de telles substances Pour minimiser l exposition à ces substances faites toujours fonction...

Page 19: ... rebut les matériaux d emballage boîte palette sangles avant d avoir terminé l inspection de l appareil Retirez la boîte extérieure et tous les matériaux d emballage de la plateforme d expédition La surface de cuisson doit être déplacée à proximité de son emplacement final Les raccordements d électricité et de gaz doivent être effectués et le dosseret installé avant le positionnement de la surface...

Page 20: ...R NOMINALE BTU HEURE ORIFICE D INJECTION MM VALEUR NOMINALE BTU HEURE BRÛLEUR C BRÛLEUR D BRÛLEUR DE PUISSANCE D GN GPL GN GPL GN GPL CPV2 488 1 90 18 500 1 00 13 000 1 90 18 500 1 10 15 000 2 20 23 500 1 24 19 000 CPV2 486GD 1 90 18 500 1 00 13 000 1 90 18 500 1 10 15 000 2 20 23 500 1 24 19 000 CPV2 486GL 1 90 18 500 1 00 13 000 1 90 18 500 1 10 15 000 2 20 23 500 1 24 19 000 CPV2 485GD 1 90 18 ...

Page 21: ...Profondeur hors tout de la surface de cuisson 28 1 8 714 28 1 8 714 28 1 8 714 E Hauteur entre le dessus du comptoir et le dessus des grilles 1 15 16 50 1 15 16 50 1 15 16 50 F Hauteur entre le comptoir et la surface supérieure du châssis 3 8 10 3 8 10 3 8 10 G Hauteur du châssis 8 3 8 213 8 3 8 213 8 3 8 213 H Distance entre le côté gauche du châssis et la ligne centrale de l admission de gaz 2 1...

Page 22: ...uverture entre les armoires 30 762 36 914 48 1 219 G Dégagement minimal entre l arrière de la surface de cuisson et la surface combustible la plus proche la surface incombustible la plus proche 6 152 0 0 6 152 0 0 6 152 0 0 H Profondeur maximale du mur jusqu au devant des armoires panneau de commande en saillie panneau de commande au même niveau que les armoires 24 3 16 614 26 5 8 677 24 3 16 614 ...

Page 23: ...CUN DOSSERET UTILISÉ INSTALLATION AU MUR Dégagement min de 0 Dégagement min de 0 Dégagement min de 0 Dégagement de 0 Surface incombustible Surface incombustible requise Surface incombustible requise Armoire à la base Armoire à la base Armoire à la base Armoire à la base Armoire à la base Armoire à la base Armoire à la base surface de cuisson surface de cuisson surface de cuisson surface de cuisson...

Page 24: ...au mur avec tablette haute voir Scénario 5 contraire La surface de cuisson doit être au même niveau que le comptoir adjacent ou au dessus de celui ci Remarque Vous pouvez également télécharger les instructions d installation du dosseret à partir de notre site Web www dcsappliances com Surfaces incombustibles telles que définies dans le National Fuel Gas Code ANSI Z223 1 édition actuelle Les mesure...

Page 25: ...hotte doivent être variables afin de réduire le niveau de bruit et la perte d air chauffé ou climatisé lorsqu une ventilation maximale n est pas requise Normalement la vitesse maximale du ventilateur est requise uniquement lors de l utilisation du gril Pour évacuer la fumée de façon optimale le bord inférieur de la hotte doit être installé à un minimum de 30 762 mm et un maximum de 36 914mm au des...

Page 26: ...ion de courant maximale du modèle indiquée dans le tableau ci dessous Veuillez vérifier la consommation de courant de votre modèle en consultant l étiquette signalétique apposée à l arrière de la cuisinière Méthode de mise à la terre requise Cet appareil est équipé en usine d un cordon d alimentation électrique muni d une fiche à trois broches avec mise à la terre à lames parallèles polarisées La ...

Page 27: ...e robinet d arrêt doit être situé à moins de 6 pieds 1 8 mètre de l appareil desservi IMPORTANT DCS par Fisher Paykel recommande d installer le robinet d arrêt manuel dans un endroit facilement accessible par le client afin qu il puisse fermer l alimentation en gaz de l appareil en cas d urgence Toutefois l appareil ne doit être modifié d aucune façon pour permettre un tel positionnement Un scella...

Page 28: ...ncoche de positionnement et les ouvertures centrales sur le dessus de l anneau de mijotage puis veillez à les insérer correctement Important Une installation incorrecte pourrait produire une flamme potentiellement dangereuse et compromettre la performance du brûleur Il n est pas possible de régler l obturateur d air sur les brûleurs de la surface de cuisson Le fonctionnement adéquat est obtenu ave...

Page 29: ...e cordon d alimentation Connexion de mise à la terre adéquate ALIMENTATION EN GAZ Raccordement NPT 1 2 avec conduite flexible de 5 8 de diamètre minimum L alimentation en gaz sur le site est compatible avec le modèle de cuisinière et une pression suffisante est disponible consultez la section Raccordement du gaz Le régulateur de pression raccordé au collecteur est réglé à 5 0 C E pour le gaz natur...

Page 30: ......

Page 31: ...16 ...

Page 32: ......

Reviews: