325.6610.17
- 40 -
For example, if it is desired to enter the letter “
K
”:
•
Press the
LETTER
button to indicate an alpha-entry is being
selected.
•
The letter group containing
“K”
is on the
“5”
button. Press the
“JKL 5”
button
•
Since
“K”
is in the second position in the letter-group, press the
“2”
button to select the letter
“K”
.
•
Repeat this procedure for the next letter.
DEFAULT CONFIGURATION:
The Chloralert Plus is pre-configured at the
factory with certain default parameter values. If these pre-programmed settings
are acceptable for the application, no further configuration concentration must
be entered by the operator, the default values will not be suitable. If the user
required additional adjustments to the factory settings, the procedures outlined
in section 4.3.3.2 through 4.3.3.7 must be used to change the instrument’s
configuration.
The unit’s default parameters are shown in Table 4-1.
If entries other than the default parameters are selected by the operator, the
operator may record these selections in the “Customer Entry” column for future
reference, if desired.
Table 4-1 Factory Default Database Parameters
MENU/SUB-MENU
PARAMETER
DEFAULT
ENTRY
CUSTOMER
ENTRY
INSTRUMENT
ENGINEERING UNITS
DISPLAY MODE
SENSOR CHECK
MANUAL
AUTO
START TIME
INTERVAL
SELF-TEST
DEFAULT DATA BASE
CUSTOM AVERAGE HOURS
CONFIGURATION CODE
PPM
MANUAL
CANCEL
DISABLE
00:00
0
SINGLE
CANCEL
0
00000000
CHANNELS
SENSOR TYPE
ALARMS - LEVEL
MODE
LATCH
DELAY
ANALOG OUTPUT - OUTPUT
SPAN
ZERO
MODE
CALIBRATION - CONCENTRATION
SPAN
ZERO
OFF
100
INST
YES
0
0.0
100
0
4-20 mA
0
DRY
DRY
DIGITAL
OUTPUTS
1 - SOURCE
2 - SOURCE
3 - SOURCE
4 - SOURCE
5 - SOURCE
6 - SOURCE
7 - SOURCE
8 - SOURCE
9 - SOURCE
INVERT (FOR ALL DIGITAL OUTPUTS)
STATE (FOR ALL DIGITAL OUTPUTS)
MALFUNCTION
CH1, A1
CH1, A2
CH2, A1
CH2, A2
CH3, A1
CH3, A2
CH4, A1
CH4, A2
NO
OFF
COMM.
PORT
BAUD RATE
INSTRUMENT ADDRESS
PARITY
DATALINK ENABLE
DATALINK PROTOCOL
9600
0
EVEN
ENABLED
STANDARD
Summary of Contents for Capital Controls CHLORALERT 17CA3000 Series
Page 14: ...325 6610 17 14 Figure 2 1 Receiver Outline Dimensions ...
Page 15: ... 15 325 6610 17 Figure 2 2 Sensor Transmitter Outline Dimensions ...
Page 16: ...325 6610 17 16 Figure 2 3 Interconnection Diagram ...
Page 18: ...325 6610 17 18 Figure 2 4 Sensor Wiring ...
Page 44: ...325 6610 17 44 ...