center so that the pegs alternate with 2 toward the
center, then 2 out from the center, all the way
around the dial except for the section now with 6
pegs out in a row (see Fig. 1).

5. Replace the cover.

Change the timer pegs back to the original pattern for
use above 50

°

F.

Figure 1: Defrost Control Timer

2.10 Low Pressure Control

If the low side refrigerant pressure drops to 15 PSIG,
the low pressure control opens and shuts off the
compressor and blower. It is an automatically reset
control. Its primary function is to prevent damage to the
compressor if a leak develops in the refrigeration
system. It may also open if the unit is A) used in a cool
area (below 50

°

F) and the defrost timer is not adjusted

(see Sec. 2.10) or B) stored where it is below 40

°

F and

then started. Under these conditions, the unit will
restart within several minutes. Until the unit warms up,
it may cycle several times.

Summary of Contents for PHOENIX 300

Page 1: ..._________________________ Read the operation and maintenance instructions carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Phoen...

Page 2: ...un Hold the switch in until the flow from the condensate hose stops 2 8 Pump Fail Light If the condensate pump fails water draining into the pump reservoir will fill above its normal level A safety fl...

Page 3: ...refrigerant pressure drops to 15 PSIG the low pressure control opens and shuts off the compressor and blower It is an automatically reset control Its primary function is to prevent damage to the comp...

Page 4: ...he unit but do not turn it on 3 Remove the air filter Slowly pour a quart of the chemical through the top grille so that it drains into the white plastic slots 4 Hold in the pump purge switch to reduc...

Page 5: ...ly but cycles on off 1 Loose connection in blower circuit Fig 3 2 Obstruction prevents impeller rotation 3 Defective blower Sec 4 5 Unit removes some water but not as much as expected 1 Air temperatur...

Page 6: ...No continuity indicates an open start winding the compressor must be replaced 5 Compressor terminals C and R No continuity indicates an open run winding the compressor must be replaced 6 Compressor t...

Page 7: ...er driers may have to be replaced to remove all of the acid and moisture NOTE NEVER use the compressor to evacuate the system or any part of it 4 6C Replacing a Compressor Non Burn Out Remove the refr...

Page 8: ...timer 4 10 Time Delay HP model only The HP model has a time delay relay in the compressor control circuit This relay delays the compressor start about 2 minutes after the power switch is turned on Thi...

Page 9: ...9 Figure 3 Electrical Schematic of Phoenix 300...

Page 10: ...4022615 1 Cord Wire Harness 12 4021908 1 Drain Hose 38 ID x 56 OD x 33 long 13 4022611 1 Outlet Collar for Ducting Outlet 14 4022593 1 Filter Drier not shown 15 4021597 1 Hour Meter 16 4021089 1 Indi...