background image

5

Figure 2: Refrigeration system of Phoenix

4.3 Troubleshooting

No dehumidification. Neither blower or compressor
run. Power switch does not light when ON.

1.

Unit unplugged or no power to outlet.

2.

Power switch defective (Sec. 2.6).

3.

Loose connection in internal wiring (Fig. 3).

No dehumidification. Neither blower or compressor
run. Power switch ON & lit.

1.

Low pressure control open (Sec. 2.11).

2.

Power switch defective (Sec. 2.6).

3.

Loose connection in internal wiring (Fig. 3).

Some dehumidification, blower runs continuously
but compressor only runs sporadically.

1.

Unit is in defrost cycle (Sec. 2.10 & 4.7).

2.

Defrost thermostat defective or loose
(Sec. 2.10 & 4.7).

3.

Loose connection in compressor circuit
(see Fig. 3).

4.

Defective compressor overload (Sec. 4.6A).

5.

Defective compressor (Sec. 4.6).

6.

Defective relay (Sec. 4.9).

7.

Defective time delay (Sec. 4.10).

No dehumidification. Blower runs but compressor
does not. Pump fail light not lit.

1.

Bad connection in compressor circuit (Fig. 3).

2.

Defective compressor capacitor (Sec. 4.6A).

3.

Defective compressor overload (Sec. 4.6A).

4.

Defective compressor (Sec. 4.6).

5.

Defective relay (Sec. 4.9).

6.

Defective time delay (Sec. 4.10).

No dehumidification. Pump Fail Light lit. Blower
runs but not compressor.

1.

Bad connection in pump circuit (Fig. 3).

2.

Pump float switch or safety switch defective
(Sec. 4.8).

3.

Pump motor defective (Sec. 4.8).

Blower does not run. Compressor runs briefly but
cycles on & off.

1.

Loose connection in blower circuit (Fig. 3).

2.

Obstruction prevents impeller rotation.

3.

Defective blower (Sec. 4.5).

Unit removes some water but not as much as
expected.

1.

Air temperature and/or humidity have dropped.

2.

Humidity meter and/or thermometer used are out
of calibration.

3.

Unit has entered defrost cycle (Sec. 2.10 & 4.7).

4.

Air filter dirty (Sec. 3.1).

5.Defrost timer incorrectly set for conditions (Sec.

2.10 & 4.7).

6.Defective defrost thermostat (Sec. 4.7)
7.

Low refrigerant charge (Sec. 4.4).

8.

Air leak such as loose cover.

9.

Defective compressor (Sec. 4.6).

10. Restrictive exhaust ducting (Sec. 2.5)

Unit runs but does not pump water.

1.

Hose kinked or plugged.

2.

Pump check valve plugged (Sec. 4.8).

3.

Bad connection in pump circuit (Fig. 3).

4.

Hose disconnected internally.

Unit pumps water automatically but not when
purge switch is pushed.

1.

Bad connection in purge switch circuit
(Fig. 3).

2.

Defective purge switch (Sec. 2.7).

Evaporator coil frosted continuously, low
dehumidifying capacity.

1.

Defrost thermostat loose or defective
(Sec. 2.10 & 4.7).

2.

Defrost timer incorrectly set or defective
(Sec. 2.10 & 4.7).

2.

Low refrigerant charge (Sec. 4.4).

3.

Dirty air filter or air flow restricted. (Sec. 3.1).

Compressor runs with power switch OFF.

1.

Defective relay (Sec. 4.10).

2.

Defective power switch (Sec. 2.6)

4.4 Refrigerant Charging

If the refrigerant charge is lost, a new charge must be
accurately weighed in. If any of the old charge is left in
the system, it must be removed before weighing in the
new charge. Refer to the unit nameplate for the correct
charge weight and refrigerant type.

Summary of Contents for PHOENIX 300

Page 1: ..._________________________ Read the operation and maintenance instructions carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Phoen...

Page 2: ...un Hold the switch in until the flow from the condensate hose stops 2 8 Pump Fail Light If the condensate pump fails water draining into the pump reservoir will fill above its normal level A safety fl...

Page 3: ...refrigerant pressure drops to 15 PSIG the low pressure control opens and shuts off the compressor and blower It is an automatically reset control Its primary function is to prevent damage to the comp...

Page 4: ...he unit but do not turn it on 3 Remove the air filter Slowly pour a quart of the chemical through the top grille so that it drains into the white plastic slots 4 Hold in the pump purge switch to reduc...

Page 5: ...ly but cycles on off 1 Loose connection in blower circuit Fig 3 2 Obstruction prevents impeller rotation 3 Defective blower Sec 4 5 Unit removes some water but not as much as expected 1 Air temperatur...

Page 6: ...No continuity indicates an open start winding the compressor must be replaced 5 Compressor terminals C and R No continuity indicates an open run winding the compressor must be replaced 6 Compressor t...

Page 7: ...er driers may have to be replaced to remove all of the acid and moisture NOTE NEVER use the compressor to evacuate the system or any part of it 4 6C Replacing a Compressor Non Burn Out Remove the refr...

Page 8: ...timer 4 10 Time Delay HP model only The HP model has a time delay relay in the compressor control circuit This relay delays the compressor start about 2 minutes after the power switch is turned on Thi...

Page 9: ...9 Figure 3 Electrical Schematic of Phoenix 300...

Page 10: ...4022615 1 Cord Wire Harness 12 4021908 1 Drain Hose 38 ID x 56 OD x 33 long 13 4022611 1 Outlet Collar for Ducting Outlet 14 4022593 1 Filter Drier not shown 15 4021597 1 Hour Meter 16 4021089 1 Indi...

Reviews: