background image

EASYLIFE

S U S T A I N A B L E   C O M F O R T ®

MW

-8

2

0

0

0

2

4

-1

ALEZIO O HYBRID

en

User Guide

Hybrid air/water heat pump

ALEZIO O HYBRID

200 ESL HYBRID 4–8

200 ESL HYBRID 11–16

Summary of Contents for 200 ESL HYBRID 11-16

Page 1: ...EASYLIFE SUSTAINABLE COMFORT MW 8200024 1 ALEZIO O HYBRID en User Guide Hybrid air water heat pump ALEZIO O HYBRID 200 ESL HYBRID 4 8 200 ESL HYBRID 11 16...

Page 2: ...sing the product and keep it in a safe place for later reference In order to ensure continued safe and efficient operation we recommend that the product is serviced regularly Our service and customer...

Page 3: ...4 4 Control panel description 25 4 4 1 Description of the keys 25 4 4 2 Description of the display 25 5 Operation 28 5 1 General 28 5 2 Use of the control panel 28 5 2 1 Browsing in the menus 28 5 2 2...

Page 4: ...es 52 8 2 Accessing the error memory 52 8 3 Troubleshooting 53 9 Decommissioning and disposal 55 9 1 Decommissioning procedure 55 9 2 Disposal and recycling 55 10 Environmental 56 10 1 Energy savings...

Page 5: ...local and national regulations Warning Do not touch the refrigeration connection pipes with your bare hands while the heat pump is running Danger of burn or frost injury Warning Do not touch the radi...

Page 6: ...rtant Allow the space required to install the appliance correctly refer to the chapter Dimensions of the Appliance Installation and Service Manual Caution Refrigerant safety Danger In the event of a r...

Page 7: ...t refer to the chapter Setting the domestic hot water temperature set point Caution Pressure limiter device refer to the chapter Special precautions to be taken when connecting the domestic hot water...

Page 8: ...he wiring according to the wiring schematics described in the chapter Electrical Connections Installation and Service Manual Caution This appliance must be connected to the protective earth Earthing m...

Page 9: ...carry out electrical connections always with the power off Caution Separate the very low voltage cables from the 230 400 V circuit cables Important The frost protection function does not work if the...

Page 10: ...consent of the manufacturer Caution To benefit from extended warranty cover no modifications must be made to the appliance Caution Do not neglect to service the heat pump Contact a qualified professio...

Page 11: ...ounts of tepid water do not remove clothing risk of adhesion to the skin If skin burns appear call a doctor immediately In the event of contact with the eyes Rinse immediately with water holding the e...

Page 12: ...Eye protection safety glasses with side protection Skin protection clothing made principally of cotton Industrial hygiene do not drink eat or smoke at the place of work Considerations on dis posal Im...

Page 13: ...rds Carry out initial commissioning and any checks necessary Explain the installation to the user If maintenance is necessary warn the user of the obligation to check the appliance and keep it in good...

Page 14: ...ecial instructions We do this to improve user safety to prevent problems and to guarantee correct operation of the appliance Danger Risk of dangerous situations that may result in serious personal inj...

Page 15: ...rd 230 V 3 Heating circuit flow 4 Circuit B flow 5 Heating circuit return 6 Circuit B return optional 7 Connection for recirculation 8 Domestic hot water outlet 9 Return from the indoor module to the...

Page 16: ...Technical data 3 2 1 Heat pump Maximum operating pressure 0 3 MPa 3 bar Tab 3 Conditions of use AWHP 4 5 MR AWHP 6 MR 3 AWHP 8 MR 2 AWHP 11 MR 2 AWHP 11 TR 2 AWHP 16 MR 2 AWHP 16 TR 2 Limit water op...

Page 17: ...ormances in accordance with EN 14511 2 Measure ment type Unit AWHP 4 5 MR AWHP 6 MR 3 AWHP 8 MR 2 AWHP 11 MR 2 AWHP 11 TR 2 AWHP 16 MR 2 AWHP 16 TR 2 Cooling out put kW 3 80 4 69 7 90 11 16 11 16 14 4...

Page 18: ...R410A gas is 2088 3 2 2 Domestic hot water tank Tab 8 Technical specifications primary circuit heating water Specification Unit Value Maximum operating temperature Version with hydraulic back up C 90...

Page 19: ...lementary heater Yes Yes Heat pump combination heater Yes Yes Rated heat output under average conditions 1 Prated kW 8 8 Rated heat output under colder conditions 1 1 Prated kW 6 6 Rated heat output u...

Page 20: ...ors LWA dB 49 61 48 64 Annual energy consumption under average conditions QHE kWh GJ 4045 6 4312 8 Annual energy consumption under colder conditions QHE kWh GJ 4564 4 4236 3 Annual energy consumption...

Page 21: ...6 5 10 1 15 4 Tj bivalent temperature Pdh kW 6 1 8 2 11 8 Tj operation limit temperature Pdh kW 5 6 6 2 8 3 Bivalent temperature Tbiv C 2 2 2 Degradation co efficient 2 Cdh 1 0 1 0 1 0 Seasonal space...

Page 22: ...ctricity consumption AEC kWh 968 968 968 Water heating energy efficiency wh 106 00 106 00 106 00 Daily fuel consumption Qfuel kWh 0 000 0 000 0 000 Annual fuel consumption AFC GJ 0 0 0 1 The rated hea...

Page 23: ...rface which comes into contact with drinking water is enamelled The indoor module is insulated by chlorofluorocarbon free polyurethane foam which helps to keep heat losses to a minimum 4 2 Operating p...

Page 24: ...em PCB EHC 02 2 Immersion sleeve for the top domestic hot water sensor 3 Flow meter 4 Plate exchanger condenser part of the heat pump 5 Immersion sleeve for the bottom domestic hot water sensor 6 3 wa...

Page 25: ...nabled Flashing symbol heating production running Steady symbol domestic hot water function enabled Flashing symbol domestic hot water production running Heating or cooling function disabled Domestic...

Page 26: ...tion is signalled by an error code and a flashing display Sub Menu COUNTERS TIME PROG sub menu Timer programming dedicated to heating and domestic hot water production Sub Menu CLOCK PCB selection men...

Page 27: ...ub menu CLK Temperature sensors Room temperature sensor connected fixed symbol for WINTER mode flashing symbol for SUMMER mode Outside temperature sensor connected fixed symbol for WINTER mode flashin...

Page 28: ...3 minutes the control panel backlight will go out Press the 2 right hand keys together to access the different menus Tab 15 Menus available Information menu User menu Installer menu Manual Forcing men...

Page 29: ...cting a PCB 1 Access the menus by pressing the two keys on the right simultaneously 2 Access the PCB selection menu only when several PCBs are present Important The PCB selection menu is available onl...

Page 30: ...3 Confirm by pressing the key 4 Select the heating shut down pressing the key The screen displays The frost protection function continues to run The heating has been shut down Important Press the key...

Page 31: ...ey 6 Go back to the main display by pressing the h key Important The display disappears after a few seconds of inactivity 5 4 3 Shutting down the cooling function Important The cooling function can be...

Page 32: ...higher than 10 C the back up shuts down and the circulating pump continues to run for a short time The radiator valves in rooms where there is a risk of frost must be fully open 5 Operation 32 200 ESL...

Page 33: ...menus of the User menu Parameter Description Factory setting Factory setting Post operation time of the circuit pump Can be set from 0 to 20 minutes 4 minutes 4 minutes Room temperature set point in...

Page 34: ...d for domestic hot water production mode Can be set from 0 to 2 Do not modify this setting 0 Domestic hot water temperature set point in comfort mode Can be set from 40 to 65 C 54 C 4 5 kW 54 C 6 kW 5...

Page 35: ...lectricity Can be set from 0 01 to 2 50 kWh 0 09 kWh Cost of fossil energy oil or gas price per litre or per m3 Can be set from 0 01 to 2 50 kWh 0 90 kWh Important AP Appliance Parameters Appliance pa...

Page 36: ...n since the last service Number of hours compressor operation since the last service hours X X Number of hours operation since the last service hours X X Number of burner start ups since the last serv...

Page 37: ...ntenance service hour run meters are reset X X Tab 25 List of parameters in the sub menu of the menu Parameter Description Timer programming for heating Timer programming for cooling only if cooling i...

Page 38: ...To set the room temperature set point in reduced mode it is necessary to set parameter available in the User menu When the setting is made in a reduced mode range this setting shortcut is used only t...

Page 39: ...can be managed via the PROG COOL sub menu dedicated to timer programming Important The flow temperature set point for the cooling mode corresponds to the parameters or depending on the type of circuit...

Page 40: ...production select the parameter available in the User menu 6 2 6 Setting the timer programming 1 Access the COUNTERS TIME PROG CLOCK menus Important When using a programmable room thermostat this men...

Page 41: ...ect the status that corresponds to the period by pressing the or key Status to for periods to Description comfort mode reduced mode 10 Confirm the selection by pressing the key 11 Repeat steps 8 to 11...

Page 42: ...PCB SCB 04 Control panel HMI Tab 30 Values available X in the sub menus Parameter Description Unit Pump rotation speed X X Control system sequence Status Important See following table X X X Control sy...

Page 43: ...mode X Heat pump flow temperature C X Heat pump return temperature C X System flow temperature C X Heating temperature set point C X Software version for the selected PCB X X X Parameter version for...

Page 44: ...al set point limited If the heating set point on the heat pump differs from the system set point pump post operation Heat pump and back up shut down system pump operation compressor bypass The back up...

Page 45: ...topped closure of the isolating valve start anti short cycle pump post operation pump post operation Heat pump and back up shut down system pump post operation operation in cooling mode normal operati...

Page 46: ...ting running The compressor and the back ups are running locking off locking forced operation in cooling mode normal operation forced operation in heating mode normal operation The compressor or the b...

Page 47: ...ompressor has stopped The back ups are operating defrosting running The compressor and the back ups are running venting normal operation The compressor or the back ups are running internal set point l...

Page 48: ...7 1 1 Troubleshooting Caution All work on the refrigeration circuit must be done by a qualified professional according to prevailing codes of practice and safety in the profession recovery of the refr...

Page 49: ...7 2 1 Cleaning the casing 1 Clean the outside of the appliance using a damp cloth and a mild detergent 7 Maintenance 7613346 v05 13112018 200 ESL HYBRID 49...

Page 50: ...ally contact a maintenance technician Tab 33 List of temporary error codes Error code Message Description H00 00 SENS T FLOW OPEN Boiler flow sensor in open circuit Heat pump flow sensor defective H00...

Page 51: ...e signal Air present in the oil circuit Flame present but flame signal weak 8 1 2 Fault codes If a fault code is still present after several automatic start up attempts the boiler switches to error mo...

Page 52: ...a maintenance technician When one of the following codes is displayed and the boiler cannot restart automatically contact a competent and qualified person Tab 35 List of alarm codes Error code Messag...

Page 53: ...no domestic hot water The domestic hot water set point temperature is too low Increase the value of parameter The domestic hot water mode is deactivated Activate the domestic hot water mode The energy...

Page 54: ...ot water tank the pipes and the taps to prevent the annoying noises likely to be produced during heating or when drawing off water The water is circulating too quickly in the central heat ing system C...

Page 55: ...ermanently 1 Contact the installer 9 2 Disposal and recycling Warning Removal and disposal of the heat pump must be carried out by a qualified professional in accordance with prevailing local and nati...

Page 56: ...ehind the radiators to prevent heat losses Insulate the pipes in rooms that are not heated cellars and lofts Close the radiators in rooms not in use Do not run hot or cold water pointlessly Install an...

Page 57: ...ble for material damage intangible losses or physical injury resulting from an installation that does not comply with Legal or regulatory requirements or provisions laid down by the local authorities...

Page 58: ...r climate conditions kW 4 3 6 4 6 5 Space heating Annual energy consumption under colder warmer climate conditions kWh GJ 3008 970 3 0 4564 1299 4 0 4236 1544 3 0 Water heating Annual energy consumpti...

Page 59: ...colder warmer climate conditions kWh 2 GJ 3 1432 664 0 0 1432 664 0 0 1432 664 0 0 Seasonal space heating energy efficiency under colder warmer climate conditions 124 169 122 167 119 161 Water heatin...

Page 60: ...lass III 1 5 Class IV 2 Class V 3 Class VI 4 Class VII 3 5 Class VIII 5 Temperature control Seasonal space heating energy efficiency of heat pump 1 If tank rating is above A use 0 95 from fiche of boi...

Page 61: ...tween the two adjacent values 2 Prated is related to the preferential space heater or combination heater Tab 40 Package efficiency temperature regulator heat pump 200 ESL Hybrid 4MR EFU C 19 200 ESL H...

Page 62: ...12 Appendix 62 200 ESL HYBRID 7613346 v05 13112018...

Page 63: ...hnological information contained in these technical instructions as well as any drawings and technical descriptions supplied remain our property and shall not be multiplied without our prior consent i...

Page 64: ...s C Salvador Espriu 11 08908 L HOSPITALET de LLOBREGAT BDR THERMEA Czech Republic s r o CZ DE DIETRICH Technika Grzewcza sp z o o PL www dedietrich cz www facebook com DeDietrichPL www dedietrich pl 4...

Reviews: