Measure
ment type
Unit
AWHP 4.5
MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
R410A re
frigerant
(3)
tCO
2
e
2.714
2.923
6.680
9.603
9.603
9.603
9.603
Refrigerant
connection
(Liquid -
Gas)
inch
1/4 - 1/2
1/4 - 1/2
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
Max. pre-
charged
length
m
7
10
10
10
10
10
10
(1) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7°C, water 55°C
(2) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7 °C, water 45 °C
for AWHP 4.5 MR only (inner and outer sides).
(3) Quantity of refrigerant calculated in tonnes of CO
2
equivalent
Important
The values in tonnes of CO
2
equivalent are calculated using the
following formula: quantity (in kg) of refrigerant fluid x GWP /
1000.
The Global-Warming Potential (GWP) of R410A gas is 2088.
3.2.2
Domestic hot water tank
Tab.8
Technical specifications primary circuit (heating water)
Specification
Unit
Value
Maximum operating temperature
Version with hydraulic back-up
°C
90
Minimum operating temperature
°C
7
Maximum operating pressure
MPa (bar)
0.3 (3.0)
Exchanger capacity
Litres
11.3
Exchange surface
m²
1.7
Tab.9
Technical specifications secondary circuit (domestic water)
Specification
Unit
Value
Maximum operating temperature
°C
80
Minimum operating temperature
°C
10
Maximum operating pressure
MPa (bar)
1.0 (10.0)
Water capacity
Litres
177
Tab.10 Common specifications (in accordance with the PR-EN 13203–5 standard)
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
AWHP 11 MR-2 ,
AWHP 11 TR-2
AWHP 16 MR-2 ,
AWHP 16 TR-2
Loading time
(1)
1 hour 21 minutes 1 hour 21 minutes 1 hour 21 minutes 1 hour 33 minutes 1 hour 11 minutes
Coefficient of performance
domestic hot water
(COP
DHW
)
0.75
0.75
0.75
1.07
1.07
(1) Water temperature set point: 57 °C – Outdoor temperature: 7°C – Inside air temperature: 20°C
3 Technical specifications
18
200 ESL HYBRID
7613346 - v05 - 13112018