Parameter Description
Adjustment
range
Factory setting
Selecting the mode for the domestic hot water Comfort period:
0 = Use the timer programs.
1 = Use the electricity tariff information input. Used to find out whether or
not production of domestic hot water is authorised (HP1 = not authorised
=> contact closed, HC0 = authorised => contact open).
2 = Use the electricity tariff information input. Used to find out whether or
not production of domestic hot water is authorised (HP1 = not authorised
=> contact open, HC0 = authorised => contact closed).
3 = Use the timer programs. The status of the electricity tariff information
input is used to activate the Boost function with compressor only (HP1 =
Boost deactivated => contact closed, HC0 = Boost activated => contact
open).
4 = The status of the electricity tariff information input is used to activate
the Boost function with compressor only (HP1 = Boost activated => con
tact open, HC0 = Boost deactivated => contact closed).
5 = The status of the electricity tariff information input is used to activate
the Boost function with compressor and back-up (HP1 = Boost deactiva
ted => contact closed, HC0 = Boost activated => contact open).
6 = The status of the electricity tariff information input is used to activate
the Boost function with compressor and back-up (HP1 = Boost activated
=> contact open, HC0 = Boost deactivated => contact closed).
0 – 6
0
Automatic switch to summer time (last Sunday in March) and to winter time
(last Sunday in October):
0 = Function not active (for countries where the time changes on other
dates or daylight saving time is not used)
1 = Function active
0 – 1
1
Domestic hot water set point in BOOST mode
40 to 70 °C
62 °C
Protection by impressed current anode
0 = Deactivation
1 = Activation
0 – 1
1
Volume of water contained in the tank (x 10 l)
6 - 255
27
Volume of water for one bath (litres)
10 - 255
120
Maximum duration of Boost mode (hours)
1 - 10
6
Back-up type:
0 = None
1 = Electrical back-up
2 = Hydraulic back-up
0 – 2
1
Time delay for start:
with electrical back-up: maximum reserved time for complete charging of
the tank in Automatic mode (hours)
with hydraulic back-up: time delay for starting the back-up in Automatic
mode (hours)
0 - 10
5
Compressor start-up time (seconds)
60 - 255
120
Activation of optimised mode. The domestic hot water tank is charged by
optimal use of the heat pump and hydraulic back-up.
0 = Optimised mode deactivated, the display is normal and the
and
parameters cannot be accessed.
1 = Optimised mode activated,
is displayed and the
and
parameters can be accessed.
0 – 1
0
6 Commissioning
48
300026515 - v09 - 25072017