Recommended positions
Fig.7
1
2
5
3
4
MW
-1
0
0
0
3
6
6
-1
1
Garage
Unheated room.
Enables recovery of the free energy released by your vehicle's engine when switched off af
ter use or by household appliances in operation.
2
Via outside air
Connection to the outside air may lead to overconsumption of electricity if the outside air
temperature falls outside the operating range.
Minimum distance to be observed for the ducts if intake and backflow are done on the same
façade: 700 mm.
Important
Risk of inconvenience in Eco operating mode: the immersion heater never
switches on. In addition, when the outdoor temperature is low, the output
of the thermodynamic water heater is reduced. The domestic hot water
set point temperature is not reached.
3
Habitable room
Can obtain free heat from the garage.
4
Laundry room
Unheated room.
Enables the dehumidification of the room and recovery of the energy wasted by washing
machines and tumble dryers.
5
Via crawl space
Connection to the crawl space is possible if the volume is greater than 30 m
3
.
The crawl space must be frost-free (temperature > 1 °C)
Important
If the crawl space is poorly insulated, thermal losses from the home will
be greater.
Position of the appliance in a cupboard
1 With EH434 (reduced elbow kit): 800 mm x 800 mm - ducted
installation
2 With EH77 or EH273: 1100 mm x 1100 mm - ducted installation
Be sure to make the air duct connections absolutely leak proof.
We strongly recommend installing the control system in the living room.
Fig.8
2
1
69
0
30
0
11
00
1100 mini
Ø 160
MW-1000367-1
Ø 160
/ 200
800 mini
800
82
6
59
8
5 Installation