7
M 300 S
11/2010 - 300003201-001 - F
3 Technical data
M 301 S
M 302 S
(1)
Power at an altitude of 400 m and at a temperature of 20°C. Calorific power of fuel oil: LHV = 11.86 kWh/kg
(2)
Fuel: domestic fuel (max viscosity 6 mm²/s to 20°C).
* min. Stage1 / min. Stage2 - max Stage2
**Separate power supply (See Electrical diagram).
Power curves according to the EN 267 standard
(1)
- M 301 S
Fire box counter pressure (mbar)
Burner
M 301-2 S
M 301-3 S
M 301-4 S
Operation
1 stage
1 stage
1 stage
Nominal output [kW]
(1)
*
77 - 166
130 - 202
184 - 261
Fuel flow [Kg/h]
(2)
*
6.5 - 14
11 - 17
15.5 - 22
Power consumption [W]
360
550
550
Nominal power of the motor [W]
260 W -
2850 tr.min
-1
380 W -
2850 tr.min
-1
380 W -
2850 tr.min
-1
Sound level at 1 m [dBA]
69
70
70
Net weight [kg]
21
21
21
Gross weight [kg]
24
24
24
Turbulance generator mark
2
3
4
Burner
M 302-1 S
M 302-2 S
M 302-3 S
M 302-4 S
M 302-5 S
M 302-6 S
Operation
2 stages
2 stages
2 stages
2 stages
2 stages
2 stages
Nominal output [kW]
(1)
*
75/98 - 142
80/113 - 160
94/181 - 217
142/192 - 275
126/202 - 430
114/179 - 460
Fuel flow [Kg/h]
(2)
*
6.3/8.2 - 12
6.7/9.9 - 13.5
7.9/15.3 - 18.3 12.0/16.2 - 23.2
10.6/17 - 36.3
9.6/15.1 - 38.8
Power consumption [W]
360
360
550
550
1000
1000
Nominal power of the motor [W]
260 W -
2850 tr.min
-1
260 W -
2850 tr.min
-1
380 W -
2850 tr.min
-1
380 W -
2850 tr.min
-1
650 W** -
2850 tr.min
-1
650 W** -
2850 tr.min
-1
Sound level at 1 m [dBA]
68
69
70
70
72
73
Net weight [kg]
22
22
22
22
30
30
Gross weight [kg]
25
25
25
25
33
33
Turbulance generator mark
1
2
3
4
5
5
G
<
H
M 301-2 S