5.4.2. Setting the air/gas ratio (Full load)
1. Unscrew the plug of the flue gas measurement
point.
2 Connect the flue gas analyser.
WARNING
Ensure that the opening around the combustion
analyzer probe is completely sealed when taking
measurements.
3. Set the boiler to full load. Press the two buttons
simultaneously. The display shows
h3
. The symbol
appears.
4. Measure the percentage of O
2
or CO
2
in the flue
gases.
5. Compare the values measured with the checking
values given in the table (Front panel removed).
6. If necessary, adjust the gas/air ratio using the
adjusting screw
(A)
.
Control and setting values O2/CO
2
at full load natural gas
Boiler type
Setting value
Checking value
O2 (%)
CO
2
(%)
O
2
(%)
CO
2
(%)
MCA Pro 45
4.7/5.0
8.9/9.1
4.5/5.1
8.8/9.2
MCA Pro 65
4.7/5.0
8.9/9.1
4.5/5.1
8.8/9.2
MCA Pro 90
4.7/5.0
8.9/9.1
4.5/5.1
8.8/9.2
MCA Pro 115
4.5/4.8
9.0/9.2
4.3/5.0
8.9/9.3
Control and setting values O
2
/CO
2
at full load for propane
Boiler type
Setting value
Checking value
O2 (%)
CO
2
(%)
O
2
(%)
CO
2
(%)
MCA Pro 45
4.4/4.8
10.6/10.8
4.3/4.9
10.5/10.9
MCA Pro 65
4.4/4.8
10.6/10.8
4.3/4.9
10.5/10.9
MCA Pro 90
Propane not available
MCA Pro 115
4.8/5.1
10.4/10.6 4.6/5.2
10.3-10.7