5. Commissioning
Parameter
Description
Adjustment range
45
65
90
115
p24
Anti-hunting/short cycling
differential for heating
system operation
5 to 59ºF
-15 to 15ºC
p25
Heat curve set point
(Maximum outdoor
temperature) WWSD (Warm
Weather Shutdown)
32 to 86ºF
0 to 30ºC
(Only with an outdoor temperature
sensor)
p26
Heat curve set point
(Supply temperature)
32 to 194ºF
0 to 90ºC
(Only with an outdoor temperature
sensor)
p27
0 to 30 ºC (Only with
an outdoor temperature
sensor) Heat curve set point
(Minimum outdoor
temperature)
-22 to 32ºF
-30 to 0ºC
(Only with an outdoor temperature
sensor
p28
Setting the pump speed
(Minimum pump speed for
heating system operation)
2 - 10 (x 10 % )
p29
Setting the pump speed
(Maximum pump speed for
heating system operation)
2 - 10 (x 10 % )
p30
Frost protection
temperature
-22 to 32ºF
-30 to 0ºC
p31
p31
Legionella protection
DHW only
0 = Off
1 = On
(After commissioning, the boiler will
operate once a week at 65°C for DHW)
3 = Management using a programmable
thermostat
p32
Set point increase for DHW
tank
-22 to 32ºF
-30 to 0 ºC
32 to 68ºF
0 to 20ºC
p33
DHW cut-in temperature
DHW sensor
35.6 to 59ºF
2 to 15ºC
p34
Control of three-way valve
0 = Normal
1 = Reverse
p35
Boiler type
0 = Heating only
1 = Open vented
p36
Shutdown input function
0 = Heating activated
1 = Shutdown without frost-protection
2 = Shutdown with frost protection
3 = Lock-out with frost protection (Pump
only)
p37
Release function
0 = Hot water on
1 = Release input
p38
Release waiting time
0 to 255 seconds
p39
Gas valve switching time
0 to 255 seconds