76249662 - v02 - 24032016
38
3 Appliance specifications
Tank type
Unit
MPLC 150
MPLC 200
Water capacity
l
150
200
Exchanger interior volume
l
7.7
10
Exchange surface
m²
0.95
1.2
Electrical power of the immersion heater
W
2200
2200
30-mA differential circuit breaker
A
16
16
Heating time (“Electric” 10 - 65°C)
h
3h35
4h45
Forced circulation - Primary at 90°C flow rate 2 m3/h
(1) (3)
Power exchanged
kW
26
29
Continuous flow
l/mn
10.7
11.8
Max. flow over 10 mn (60°C storage)
l/10 mn
235
302
Heating time (10- 60°C)
mn
30
30
Forced circulation - Primary at 60°C flow rate 2 m3/h
(1) (3)
Power exchanged
kW
8.8
9.7
Continuous flow
l/mn
3.6
4
Max. flow over 10 mn (60°C storage)
l/10 mn
163
214
Heating time (10- 50°C)
mn
95
95
Thermosiphon - Primary at 90°C
(1) (2) (3)
Power exchanged
kW
17.5
19.2
Continuous flow
l/mn
7.1
7.8
Max. flow over 10 mn (60°C storage)
l/10 mn
217
282
Heating time (10- 60°C)
mn
50
50
Maintenance consumption at 65°C
kWh/24h
1.62
2.16
Weight
kg
51
62
(1) The performance levels above apply to tanks in the vertical position. Allow a 10% reduction for horizontal installations.
(2) Thermosiphon: the performance levels are given for a non-resistant installation (ø 1”1/4) with 4 bends, the bottom of the
water heater being at least 2 m above the boiler.
(3) Domestic cold water at 10°C - Domestic hot water at 45°C.
MPL
Tank
Exchanger
Max. temperature
90°C
100°C
Max. pressure
6 bar
3 bar
Warning:
The operating pressure of the heat exchanger circuit must not
exceed 3 bar - 0.3 MPa, and its temperature must not exceed
100°C.
3 Technical specifications