background image

DEEKAX  Air Oy

Patruunapolku 4            Puh. 0207 912550
79100 LEPPÄVIRTA      www.deekaxair.fi    

 

PURE JOY FROM INDOOR AIR ! 

MAINTENANCE OF TALTERI  

For producing good indoor climate continuously, the air exchange systems require regular maintenance. 
The metallic grease filter of stove hood must always be kept clean for fire safety reasons. Cleansing with hot 
water dishwasher once a month is necessary. Substances suitable for machine washing may darken the 
aluminium parts of the filter. 
The inlet and outlet filters of Talteri must be cleansed at least twice a year.  

                                                                                            

In summertime the summer cassette plate will be set to summer mode

 

when the external air should come in fresh and clean. 
 
The heat recovery cell will be pulled out of the unit and washed thoroughly in autumn just before the heating 
season begins –the heat recovery will then be at its best. Check the condition of sealing and push the heat 
recovery cell back to its place. 
 

 

The inner painted walls of the unit are easy to clean. Check the condition of sealing, clean the outlet hose of 
condensing water and make sure the water flows freely and without any obstructions. 
 
The impellers, air exchange adjusters and thermostats are components that do not require regular 
maintenance. Electrical works can be carried out only by a qualified electrician.  
 
 
During  the frosty period the heat recovery cell is defrozen  by using the preheater.  The power of the 
preheater is mainly adequate to keep  the  heat recovery cell defrozen. 

In extreme conditions, if the power of 

the preheater is not sufficient, the supply fan power will be reduced or stopped by the freezing protection 
thermostat when the exhaust air temperature drops below the set value (0°C). The supply fan starts when 
the exhaust air temperature rises above the set value. 

 
 
 
Under extreme conditions (humidity /harsh cold) the Ito-element may freeze over and the anti-freeze 
protection series are not able to defrost it. If such a case occurs, the machine has to be stopped, opened and 
the cold flow stopped and the ice given the necessary time to melt. Check the drainage of condensing water! 
In case the water-lock dries out and makes pulping noise, you can pour a drop or two of cooking oil.

 

 
In really cold weather, the head recovery unit heats the preheated inlet air with afterheating. The functionality 
can be proved by comparing the temperature of inlet air to the set value of the inlet air afterheating. 
 
The overheat protection has been activated in case the temperature has risen +90 

o

C (for instance, in case 

of power failure). Reset the overheat temperature by pressing the switch under the threaded contact 
protection.  

 

The channels must be checked if the impeller works but the air exchange is inadequate or the temperature 
changes in the channels between the interior and the machine. Temperature changes and humidity 
concentration in channels must be prevented by improving the isolation.    

Summary of Contents for DIVK-C220 DEMA

Page 1: ... THE RECOVERY SYSTEM TALTERI removes used air from interior and brings in fresh air Humidity and impurities are exhausted through thermal recovery unit that heats the filtered ambient air cost effectively The fresh warm air is channelled draught free and noise free into the premises in necessary quantities ENSURE THE QUALITY OF AIR EXCHANGE DIVK C220 DEMA and DIVK C220 DEMA VKL QUALITY TESTED ...

Page 2: ...EC 520W 8 Exhaust fan adjustable EC 520W 9 Heat exchanger 10 Suply air filter F7 ISO ePM1 11 Exhaust air filter G4 ISO Coars 75 12 Condessing water outlet 12 mm 13 Operating panel 14 Preaheater 1000W manual overheat protection 15 Afterheat 1000W manual overheat protection or VKL water battery actuator 16 Summer bypass appliance Flow rate DIMMENSIONS Height 950 mm Widht 1100 mm Depth 510 mm Weight ...

Page 3: ...outside air will be obtained through grate without an insect net The air inlet will be situated to as clean space as possible far from the refuse discharge smokestack ventilation outlet and exhaust air tube The air inlet will be located to a height of at least 2 meters from ground on the northern side of the building opposite side to the traffic Due to warm summer weather the outlet channel has to...

Page 4: ...k built from condensate hose If an outside condensate hose lock is used the machine s own water lock must be removed and make sure that the condensate hose is downward If the water hose is connected to a 32 mm sewer pipe imported inside the wall it is necessary to seal the joint so that no water vapor enters the electrical connection underneath the machine In this case the intake air supply must b...

Page 5: ... V voltage signal from Control panel The voltage signal connected to CO2 RH1 terminal Sensor 1 EXT can be operated through maintenance menu of the operating panel The boosting of Talteri ventilation unit can controlled with Ultra KTS cooker hood There is a control panel and when the closing damper of the cooker hood is open the fan speed is enhanced Maintenance menu is used to set boost 0 there ca...

Page 6: ...0 0 10 COOLING 24 0 WATER HEATER FILTER 24 0 HEAT RECOVERY BYPASS WINTER YHT SUMMER ALARM NC YHT NO Control board ECU R EXTRACT SUPPLY 0 10 0 10 0 0 SUPPLY EXTRACT N N U U N 4 L 1 L 2 N 3 L N E J 50c 90c 1000W 1 2 3 Belimo LM 24 2A 1A 5B 4B SWITCH ON OFF N L s k 0 10v 0 10v GND GND COM NC COM NC wh 1 wh 2 N L s k wh 1 wh 2 2 1 3 2 1 3 MODBUS A D B D 0 O O O O O O O O O ON OFF BIAS B ON OFF Term ON...

Page 7: ...ater pipe installed in the top of the vent valve Both the supply and return pipes are fitted with shut off valves A safety device in case of power failure will be open air duct of the horizontal part install a spring loaded shut off damper control may be the tip of data in the machine or spring closing damper which prevents the wind pressure of air flowing to happen freeze through the machine and ...

Page 8: ...eck the pressure level of thechannels by checking from the fans and adjust it accordingly to obtain the pressure level of 10 30 Pa for fans adjust and lock the pattern Draw measuring and adjustment records USAGE AND CORRECT LEVEL OF AIR EXCHANGE The air exchange level is regulated by changing the working speed of the air impeller from the operating panel Airflow of different adjustable positions c...

Page 9: ... fan 5 DEFAULT SETTINGS 1 30 2 40 3 60 4 80 5 100 FAN SPEED PRESELCTION BOOSTING FROM THE COOKER HOOD WITH CONTACT TIP INFORMATION Intensification time settings 0 and 5 120 min In 0 position with different pre data Intensification limit settings 1 4 the air impellers higher than basic speed CO2 AND or RH SENSORS ACTIVATION CO2 AND HUMIDY PERCENTAGE SETTING Note set the sensor on in the settings me...

Page 10: ...RE or EXT TIME INTENSIFICATION AND AFTERHEATING OPERATING PANEL USER INSTRUCTION MAIN DISPLAY AND ADJUSTMENT OF BLOWING SPEED EDIT FUNCTIONS RETURN EDIT SET SET SET Touch screen buttons Boosting Fireplace switch pressure compensation Out of house mode Fan speed adjustment 1 5 SET EDIT EDIT EDIT The button can be used to browse the menu upwards and change settings The button can be used to browse t...

Page 11: ...witching Setting of RH upper limit Set value 30 80 5 steps Regulating amplitude 5 20min Touch screen buttons Boosting Fireplace switch pressure compensation Out of house mode Fan speed adjustment 1 5 The button can be used to browse menu upwards and change settings The button can be used to browse menu downwards and change setting value Return previous or main menu The summer bypass plate control ...

Page 12: ...pressure activated OFFICE continuation time activated Modbus Touch screen buttons Boosting Extended time office mode Out of house mode Fan speed adjustment 1 5 The button can be used to browse menu upwards and change settings The button can be used to browse menu downwards and change setting value Return previous or main menu Inlet air cooling temperature 10 15 o C Inlet air heating temperature 30...

Page 13: ...ferent pre data Overpressure limit regulation 1 4 inlet air impeller higher than outlet air impeller Intensification time settings 0 and 5 120min In 0 position with different pre data Intensification limit settings 1 4 the air impellers higher than basic speed BACKLIGHT BRIGHTNESS AND STANDBY SCREEN Adjustment of backlight Press and hold the FUNCTIONS for about 5 seconds Options not in use time an...

Page 14: ...s is selectable by the user New push from the switch launches overpressurization from the beginning Overpressurization can be shut down also from operating panel Anti freeze is deactivated when overpressurization is switched on 3 3 Intensification Intensification of air exchange can be activated from the operating panel or stove hood Activation from the panel sets the durability of intensification...

Page 15: ...ance menu When the air temperature is lower than set the information will be displayed on operating panel and red indication light is turned on The inlet impeller is stopped and the speed of outlet impeller is reduced to minimum These actions prevent the water circulation battery from freezing 5 3 Income air too hot Maximum limit of income air temperature must be set from the maintenance menu When...

Page 16: ... is defrozen by using the preheater The power of the preheater is mainly adequate to keep the heat recovery cell defrozen In extreme conditions if the power of the preheater is not sufficient the supply fan power will be reduced or stopped by the freezing protection thermostat when the exhaust air temperature drops below the set value 0 C The supply fan starts when the exhaust air temperature rise...

Reviews: