Water heater power
When installing TALTERI equipped with a water radiator (VKL model):
- During the design phase, the temperatures of the water used should be taken into account and the
adequacy of the heating capacity under sizing conditions should be checked.
- The heating coil is connected to a 15 mm copper or similar plastic tube
- Future Machine of water must be pre-adjusted after the boiler going water heating coil is connected to
the actuator, which controls water flow to the radiator
- Radiator return water pipe installed in the top of the vent valve
- Both the supply and return pipes are fitted with shut-off valves
- A safety device in case of power failure will be open-air duct of the horizontal part
install a spring-loaded shut-off damper (control may be the tip of data in the machine),
or spring closing damper, which prevents the wind pressure of air flowing to happen
freeze through the machine and water heater. Damper axle must be in an upright position
.
70
o
C 50
o
C 0,07 l/s 150 l/s 5/39 6,1
kW
50
o
C 35
o
C 0,06l/s 150 l/s 5/27
35
o
C 26
o
C 0,07 l/s 150 l/s
5/20 2,7
kW
4,0
kW
DIVK-C 220 DEMA VKL R
DIVK-C 220 DEMA VKL L
coming
water
return
water
water
flow
air
flow
rise of the
temperature
total
power