INTRODUCTION OF THE AIR EXCHANGE SYSTEM 

BEFORE OPERATING YOUR AIR EXCHANGE SYSTEM, 
MAKE SURE THAT: 

- There are no loose objects within the unit or the air impeller; 
- The coverings of construction-time are removed from  
   the outlet- and exhaust air holes; 
- All isolations and steam barriers are in order; 
- The heat transfer and fans are in their places; 
- The condensing water outlet is installed and the water  
   is drained out; 
- The air impellers and their adjusters are in working order; 
- Afterheating is regulated and working. 

USAGE DURING INSTALLING 

     The air exchange unit should be started as soon as 
 installation permits. 
Efficient air exchange promotes drying of the constructions 
 and prevents damage. 
In case channelling has not been completed, fans and adjustments 
are missing,filter paper must be used in place of fans to keep  
the channels clean andprovide sufficient counterpressure for  
preventing overload. The unit must be used with full power and  
check the drainage of the condensing water.  
The appliance, filters and heat exchangers must be cleaned  
and the systemadjusted after the construction works are 
completed. 

BASIC ADJUSTMENT OF AIRFLOW 

     The unit alone can not produce good interior ear in case  
the channels and fans are installed carelessly and main  
adjustments are not made.  
Regulate the inlet and outlet fans to the planned positions  

and start the unit 
at design power speed. Measure the airflow in outside- and 
 exhaust air channels. 
The outlet must be 5-15% higher than inlet. Check the  
pressure level of thechannels by checking from the fans and  
adjust it accordingly to obtain the pressure level of 10-30 Pa  
for fans; adjust and lock the pattern.Draw measuring- and  
adjustment records! 

USAGE AND CORRECT LEVEL OF AIR EXCHANGE 

     The air exchange level is regulated by changing the  
working speed of the air impeller from the operating panel. 
Airflow of different adjustable positions can be seen  
from table on  page  2. 
Adjustable position 1 is for basic air exchange for an empty house. 
Adjustable position 2 and 3 are normal working positions. 
Adjustable position 4 and 5 are efficiency positions (i.e. for saunas). 
The correct usage positions will be found by experience; 
observing the purity of the air or sultriness when coming in 
from outside, observing moisture on the windows or drying 
of the sauna. 

AFTERHEATING AND SUMMER BYPASS OF INLET AIR 

     The unit is equipped with 1000W electrical battery operated 
by the means of triac-adjuster or a water battery (VKL) operated by 
the operating device for afterheating the heat recovered inlet air. 
The temperature of inlet air is usually regulated to +16C.  
The temperature may be adjusted to higher during winter so there 
would be no draught like feeling. In case of severe frost and 
efficiency mode the heating power might turn out insufficient – 
in such circumstances, the air exchange should be reduced. 
The overheating protection launched during malfunctioning 
must be annulled manually. 
During summertime, the  heat recovery exchanger element  
on the bypass platewill be closed so the exhaust air will not  
warm up the inlet air.   
      

THE SUMMER BYPASS OF THE UNIT MUST BE IN  THE WINTER POSITION WHEN THE AIR FLOWS ARE BEING ADJUSTED

Summary of Contents for DIVK-C220 DEMA

Page 1: ... THE RECOVERY SYSTEM TALTERI removes used air from interior and brings in fresh air Humidity and impurities are exhausted through thermal recovery unit that heats the filtered ambient air cost effectively The fresh warm air is channelled draught free and noise free into the premises in necessary quantities ENSURE THE QUALITY OF AIR EXCHANGE DIVK C220 DEMA and DIVK C220 DEMA VKL QUALITY TESTED ...

Page 2: ...EC 520W 8 Exhaust fan adjustable EC 520W 9 Heat exchanger 10 Suply air filter F7 ISO ePM1 11 Exhaust air filter G4 ISO Coars 75 12 Condessing water outlet 12 mm 13 Operating panel 14 Preaheater 1000W manual overheat protection 15 Afterheat 1000W manual overheat protection or VKL water battery actuator 16 Summer bypass appliance Flow rate DIMMENSIONS Height 950 mm Widht 1100 mm Depth 510 mm Weight ...

Page 3: ...outside air will be obtained through grate without an insect net The air inlet will be situated to as clean space as possible far from the refuse discharge smokestack ventilation outlet and exhaust air tube The air inlet will be located to a height of at least 2 meters from ground on the northern side of the building opposite side to the traffic Due to warm summer weather the outlet channel has to...

Page 4: ...k built from condensate hose If an outside condensate hose lock is used the machine s own water lock must be removed and make sure that the condensate hose is downward If the water hose is connected to a 32 mm sewer pipe imported inside the wall it is necessary to seal the joint so that no water vapor enters the electrical connection underneath the machine In this case the intake air supply must b...

Page 5: ... V voltage signal from Control panel The voltage signal connected to CO2 RH1 terminal Sensor 1 EXT can be operated through maintenance menu of the operating panel The boosting of Talteri ventilation unit can controlled with Ultra KTS cooker hood There is a control panel and when the closing damper of the cooker hood is open the fan speed is enhanced Maintenance menu is used to set boost 0 there ca...

Page 6: ...0 0 10 COOLING 24 0 WATER HEATER FILTER 24 0 HEAT RECOVERY BYPASS WINTER YHT SUMMER ALARM NC YHT NO Control board ECU R EXTRACT SUPPLY 0 10 0 10 0 0 SUPPLY EXTRACT N N U U N 4 L 1 L 2 N 3 L N E J 50c 90c 1000W 1 2 3 Belimo LM 24 2A 1A 5B 4B SWITCH ON OFF N L s k 0 10v 0 10v GND GND COM NC COM NC wh 1 wh 2 N L s k wh 1 wh 2 2 1 3 2 1 3 MODBUS A D B D 0 O O O O O O O O O ON OFF BIAS B ON OFF Term ON...

Page 7: ...ater pipe installed in the top of the vent valve Both the supply and return pipes are fitted with shut off valves A safety device in case of power failure will be open air duct of the horizontal part install a spring loaded shut off damper control may be the tip of data in the machine or spring closing damper which prevents the wind pressure of air flowing to happen freeze through the machine and ...

Page 8: ...eck the pressure level of thechannels by checking from the fans and adjust it accordingly to obtain the pressure level of 10 30 Pa for fans adjust and lock the pattern Draw measuring and adjustment records USAGE AND CORRECT LEVEL OF AIR EXCHANGE The air exchange level is regulated by changing the working speed of the air impeller from the operating panel Airflow of different adjustable positions c...

Page 9: ... fan 5 DEFAULT SETTINGS 1 30 2 40 3 60 4 80 5 100 FAN SPEED PRESELCTION BOOSTING FROM THE COOKER HOOD WITH CONTACT TIP INFORMATION Intensification time settings 0 and 5 120 min In 0 position with different pre data Intensification limit settings 1 4 the air impellers higher than basic speed CO2 AND or RH SENSORS ACTIVATION CO2 AND HUMIDY PERCENTAGE SETTING Note set the sensor on in the settings me...

Page 10: ...RE or EXT TIME INTENSIFICATION AND AFTERHEATING OPERATING PANEL USER INSTRUCTION MAIN DISPLAY AND ADJUSTMENT OF BLOWING SPEED EDIT FUNCTIONS RETURN EDIT SET SET SET Touch screen buttons Boosting Fireplace switch pressure compensation Out of house mode Fan speed adjustment 1 5 SET EDIT EDIT EDIT The button can be used to browse the menu upwards and change settings The button can be used to browse t...

Page 11: ...witching Setting of RH upper limit Set value 30 80 5 steps Regulating amplitude 5 20min Touch screen buttons Boosting Fireplace switch pressure compensation Out of house mode Fan speed adjustment 1 5 The button can be used to browse menu upwards and change settings The button can be used to browse menu downwards and change setting value Return previous or main menu The summer bypass plate control ...

Page 12: ...pressure activated OFFICE continuation time activated Modbus Touch screen buttons Boosting Extended time office mode Out of house mode Fan speed adjustment 1 5 The button can be used to browse menu upwards and change settings The button can be used to browse menu downwards and change setting value Return previous or main menu Inlet air cooling temperature 10 15 o C Inlet air heating temperature 30...

Page 13: ...ferent pre data Overpressure limit regulation 1 4 inlet air impeller higher than outlet air impeller Intensification time settings 0 and 5 120min In 0 position with different pre data Intensification limit settings 1 4 the air impellers higher than basic speed BACKLIGHT BRIGHTNESS AND STANDBY SCREEN Adjustment of backlight Press and hold the FUNCTIONS for about 5 seconds Options not in use time an...

Page 14: ...s is selectable by the user New push from the switch launches overpressurization from the beginning Overpressurization can be shut down also from operating panel Anti freeze is deactivated when overpressurization is switched on 3 3 Intensification Intensification of air exchange can be activated from the operating panel or stove hood Activation from the panel sets the durability of intensification...

Page 15: ...ance menu When the air temperature is lower than set the information will be displayed on operating panel and red indication light is turned on The inlet impeller is stopped and the speed of outlet impeller is reduced to minimum These actions prevent the water circulation battery from freezing 5 3 Income air too hot Maximum limit of income air temperature must be set from the maintenance menu When...

Page 16: ... is defrozen by using the preheater The power of the preheater is mainly adequate to keep the heat recovery cell defrozen In extreme conditions if the power of the preheater is not sufficient the supply fan power will be reduced or stopped by the freezing protection thermostat when the exhaust air temperature drops below the set value 0 C The supply fan starts when the exhaust air temperature rise...

Reviews: