SETUP MENU
Maintenance interval and reset
Display sensor and overheating faults,
temperature deviations, filter exchange and starts
Fault list reset
Air exchange can be reduced/increased during selected time periods.
5 different periods can be programmed. Each time period can be set for one or several weekdays.
In office-mode, the unit stops for the period out of selection and display reads standby.
Weekday and clock selection
CO
2
transmitter ON/OFF switching.
Setting of CO
2
upper limit.
Set value 250...1500ppm, 50ppm steps
Regulation of the inlet air afterheating set value
5...30
o
C
SETTINGS
Fan speed adjustment 1....5
%RH transmitter ON/OFF switching.
Setting of RH upper limit.
Set value 30...80%, 5% steps
Regulating amplitude 5...20min
Touch screen buttons:
Boosting
Fireplace switch
(pressure compensation)
Out-of-house mode
Fan speed adjustment 1....5
The button can be used to browse
menu upwards and change settings.
The button can be used to browse
menu downwards and change setting value.
Return previous or main menu.
The summer bypass plate control. The user of the unit can set the bypass plate manually to
SUMMER/WINTER or AUTOMATIC mode
In summer mode the bypass plate is activated
During the automatic mode, the plate works according to outside temperature. Set value 15...20
o
C
The automatic mode has adjustment amplitude of approx 2 hours
Set value of intensification duration
0 and 5…120 min.
In 0 position different switch pre-data.
Set value of overpressure duration time
(hearth switch) 5…30 min.
In 0 position different switch pre-data.
.