3.7. Office mode 

The installer can select the office mode from the maintenance menu – this is useful in case the air exchange system is installed 
into an office where activities take place mostly during daytime. The speeds are controlled by the weekly clock. 
The mode is equipped with continuation switch that enables persons who remain in the office for longer to prolong the 
functioning of the appliance by set interval. Intensification and out-of-house mode functions are not usable in the office mode.  
Remote control mode can also be selected from the maintenance menu that enables to switch the unit on and off by the mean of 
pre-programmed data and weekly clock functions are deactivated. 
 

4. Setting the temperature 

Temperature is measured from four different sources: temperature outside, inlet temperature, outlet temperature and exhaust air 
temperature. The temperatures are displayed on the operating panel. The precision of measurement is +/- 1 degree. 

4.1. Afterheating 

The thermostat leads the afterheater located in the inlet channel. The heater can be electrical or water heater and is selected by 
the installer from the maintenance menu. The heater keeps inlet air at the exact temperature selected by the user. The desired 
temperature can be set from the operating panel. Set values are between 5 – 30 degrees.  

4.2. Preheating 

Preheater is an electric heater located in the outlet channel. The preheater´s thermostat is driven based on the temperature of 
exhaust air. Preheating is meant for prevent freezing of the recovered heat. The temperature setting of the thermostat can be 
selected by the installer from the maintenance menu with limitations of 0 – 10 degrees.  

4.3. Summer cassette function 

The unit is equipped with summer cassette for heat exchange during summertime. The user can select the function manually or 
let the functioning be determined automatically according to the temperature outside. During the Summer-mode, the bypass plate 
of the cassette is activated.  
The automatic functioning can be set with external temperature between 15 – 20 degrees. 

5. Alarms and reminders 

5.1. Activation of overheat protection 

Information on activation of overheats protection connected to electrical afterheater and preheater is received from the heater. In 
case the protection launches, the impellers are automatically set on minimum speed, red indicator light blinks on the operating 
panel and the display informs about malfunctioning.  

5.2. Inlet air too cold 

Inlet air minimum temperature must be set from the maintenance menu. When the air temperature is lower than set, the 
information will be displayed on operating panel and red indication light is turned on. The inlet impeller is stopped and the speed 
of outlet impeller is reduced to minimum. These actions prevent the water-circulation battery from freezing.  

5.3. Income air too hot 

Maximum limit of income air temperature must be set from the maintenance menu. When the air temperature exceeds the set 
limits, respective information will be displayed on operating panel and red indication light is turned on. The inlet impeller is 
stopped and the speed of outlet impeller decreased to minimum. 

5.4. Exhaust air too cold 

The exhaust air temperature minimum limits must be set from the maintenance menu (-10 … 10 degrees). When the air 
temperature is lower, warning is displayed on the operating panel and red indication light is turned on. The temperature is 
attempted to keep above the set value by reducing the speed of inlet air impeller (see also preheating) by regulating it one-step at 
a time. In case the air temperature does not rise over the alarm limit even when the impeller is completely stopped, the red 
indication light starts to blink and freezing alert is displayed. In case the temperature is restored to normal, normal functioning 
will be also restored by increasing the impeller speed one-step at a time.   

5.5. Danger of water battery freezing 

In VKL machines can be set the temperature of the water radiator from the service menu “radiator return min temp” 
and when the value falls down, a notification is displayed and the red indicator lights up in the control panel. The inlet 
fan is stopped.  

5.6. Alarms for remote monitoring 

General alerts may be taken into the remote control from potentially free relay. Alarms are obtained inlet air hot or 
cold, danger of water battery freezing, overheat protectors and if the machine is stopped.

 

5.7. Maintenance interval reminder 

When the maintenance interval is complete, the respective information is displayed on the operating panel and the indication 
light blinks green. The user can reset the reminder after the filters have been changed. The maintenance interval counter is reset 
and the new alert will be transmitted after the period has been completed again. The maintenance interval can be set between 3 – 
12 months.  

5.8. Filter-dirty notice 

Differential pressure switch can be installed to the equipment that measures dirtiness of the inlet air filter by monitoring its 
differential pressure. When the switch runs, the display transmits the necessity of filter-change and the indication light blinks 
yellow. Differential pressure switch is taken into use through the maintenance menu and it deactivates maintenance interval 
reminder

 

Summary of Contents for TALTERI DIVK-C330 DEMA

Page 1: ... THE RECOVERY SYSTEM TALTERI removes used air from interior and brings in fresh air Humidity and impurities are exhausted through thermal recovery unit that heats the filtered ambient air cost effectively The fresh warm air is channelled draught free and noise free into the premises in necessary quantities ENSURE THE QUALITY OF AIR EXCHANGE DIVK C330 DEMA and DIVK C330 DEMA VKL QUALITY TESTED ...

Page 2: ... ISO Coars 75 13 Supply air filter F7 ISO ePM1 15 Operating panel 16 Overheat protection of the preheater manual reset 17 Overheat protection of the postheater manual reset 18 Summer bypass appliance motorized 19 Condessing water outlet 20 Differential pressure switch supply 21 Differential pressure switch extract 2 15 In the picture shown right handed model R EC speeds preselection is performed f...

Page 3: ... AND EXHAUST AIR The outside air will be obtained through grate without an insect net The air inlet will be situated to as clean space as possible far from the refuse discharge smokestack ventilation outlet and exhaust air tube The air inlet will be located to a height of at least 2 meters from ground on the northern side of the building opposite side to the traffic Due to warm summer weather the ...

Page 4: ... position of the unit and free flow of the condensing water Condensing Condensate drain is connected to the machine condensate connector 3 8 external thread Condensate can be made at a least 10 mm in the bore copper pipe or Relatively stiff hose The water pipe Making about 10 cm in the water trap and the tube is connected to a floor drain The water line shouldnt be connected directly to the sewer ...

Page 5: ...erator panel Spring return damper motor connection The damper motor closes the machine stopped the machine in standby mode the machine alarm tip supply fan information max 2A 250V tip extract fan information max 2A 250V alarm summer bypass sensor 1 sensor 2 Overpressure extended time boosting away remote filter cooling water radiator The fan speed of Talteri ventilation unit can be controlled with...

Page 6: ...U_M Operator panel TEMPERATURE SENSORS 6 DIVK C330 DEMA VKL T1 T2 T3 T4 T5 T6 OUT DOOR SUP PLY EXTR EX HAUST WATER PRE HEATER POST HEATER 230VAC L N PE FUSE TEMPERATURE SENSOR 24 0 0 10 CO2 RH1 24 0 0 10 CO2 RH2 0 10 24 0 0 10 24 0 24 0 SUMMER BYPASS WIN TER YHT SUM MER ALARM NC YHT NO R EXTRACT SUPPLY 0 10 0 10 0 0 SUPPLY EXTRACT N N U U A1 A2 L1 L2 L3 13 N 14 T1 T2 T3 L 2 L 1 N N E J COM NC COM ...

Page 7: ...alves A safety device in case of power failure will be open air duct of the horizontal part install a spring loaded shut off damper control may be the tip of data in the machine or spring closing damper which prevents the wind pressure of air flowing to happen freeze through the machine and water heater Damper axle must be in an upright position 70 c 50 c 0 11 l s 300 l s 5 30 9 0 kW 70 c 50 c 0 0...

Page 8: ...f condensate water is prevented by a dual acting antifreeze function which first turns the preheater on and later switches it off when the temperature rises above the set value If the power of the preheater is not sufficient and the waste air temperature drops below the waste air cold limit the supply fan power is incrementally reduced until the waste air cold limit value is reached MAKE SURE THAT...

Page 9: ...DEFAULT SETTINGS 1 30 2 40 3 60 4 80 5 100 FAN SPEED PRESELCTION BOOSTING FROM THE COOKER HOOD WITH CONTACT TIP INFORMATION Intensification time settings 0 and 5 120 min In 0 position with different switch pre data Intensification limit settings 1 4 the air impellers higher than basic speed CO2 AND or RH SENSORS ACTIVATION CO2 AND HUMIDY PERCENTAGE SETTING Note set the sensor on in the settings me...

Page 10: ...RE or EXT TIME INTENSIFICATION AND AFTERHEATING OPERATING PANEL USER INSTRUCTION MAIN DISPLAY AND ADJUSTMENT OF BLOWING SPEED EDIT FUNCTIONS RETURN EDIT SET SET SET Touch screen buttons Boosting Fireplace switch pressure compensation Out of house mode Fan speed adjustment 1 5 SET EDIT EDIT EDIT The button can be used to browse the menu upwards and change settings The button can be used to browse t...

Page 11: ...switching Setting of RH upper limit Set value 30 80 5 steps Regulating amplitude 5 20min Touch screen buttons Boosting Fireplace switch pressure compensation Out of house mode Fan speed adjustment 1 5 The button can be used to browse menu upwards and change settings The button can be used to browse menu downwards and change setting value Return previous or main menu The summer bypass plate control...

Page 12: ...pressure activated OFFICE continuation time activated Modbus Touch screen buttons Boosting Extended time office mode Out of house mode Fan speed adjustment 1 5 The button can be used to browse menu upwards and change settings The button can be used to browse menu downwards and change setting value Return previous or main menu Inlet air cooling temperature 10 15 o C Inlet air heating temperature 30...

Page 13: ...t switch pre data Overpressure limit regulation 1 4 inlet air impeller higher than outlet air impeller Intensification time settings 5 120min In 0 position with different switch pre data Intensification limit settings 1 4 the air impellers higher than basic speed BACKLIGHT BRIGHTNESS AND STANDBY SCREEN Adjustment of backlight Press and hold the FUNCTIONS for about 5 seconds Options not in use time...

Page 14: ...s is selectable by the user New push from the switch launches overpressurization from the beginning Overpressurization can be shut down also from operating panel Anti freeze is deactivated when overpressurization is switched on 3 3 Intensification Intensification of air exchange can be activated from the operating panel or stove hood Activation from the panel sets the durability of intensification...

Page 15: ...ance menu When the air temperature is lower than set the information will be displayed on operating panel and red indication light is turned on The inlet impeller is stopped and the speed of outlet impeller is reduced to minimum These actions prevent the water circulation battery from freezing 5 3 Income air too hot Maximum limit of income air temperature must be set from the maintenance menu When...

Page 16: ...o keep the heat recovery cell defrozen In extreme conditions if the power of the preheater is not sufficient the supply fan power will be reduced or stopped by the freezing protection thermostat when the exhaust air temperature drops below the set value 0 C The supply fan starts when the exhaust air temperature rises above the set value During the frosty period the heat recovery cell is defrozen b...