Installation
057-179 ISSUE: 3
Page 14 of 50
4.4 TYPICAL CONNECTION TO DSE CONTROLLERS
This section shows how to connect DSE controllers to the gateway device.
4.4.1 ADDING THE CONTROLLER TO THE DSE892
To ensure newly added controllers are recognised by the DSE892, the following steps must be
followed. Failure to do so may result in communications failure, indicated by a RED communications
port LED.
The DSE892 is factory set to accept connection via the USB port. If this is not the port to be
used, you must configure the DSE892 for the required port as detailed elsewhere in this
document.
Remove the DC supply from the DSE892 AND the connected controller(s).
Connect the new controller to the chosen communications port.
Apply the DC supply to the controller being connected (and any other controllers in the
system).
Reapply the DSE supply to the DSE892 Gateway.