4
Dimensions without cable glands:
150 x 170 x 65 mm (WxHxD)
Weight:
2,1 kg
Capacity of the internal memory of history:
44 days at 60s recording interval
Interval record storage memory:
60 s (adjustable range 1-255 s)
Dead band:
max 5 % of range
Consumption/input at 24V (output RS485)
Warm-Up time
DEGA NSx-EL III LCD
90 mA/2,2 W
DEGA NSx-EL III LCD
max. 180 s
DEGA NSx-CL III LCD
135 mA/3,3 W
DEGA NSx-CL III LCD
max. 30 s
DEGA NSx-IL III LCD
115 mA/2,8 W
DEGA NSx-IL III LCD
max. 15 s
DEGA NSx-SL III LCD
135 mA/3,3 W
DEGA NSx-SL III LCD
max. 180 s
DEGA NSx-PL III PID LCD 154 mA/3,4 W
DEGA NSx-PL III PID LCD
max. 30 s
Consumption/input at 24V (output 4-20mA)
Time to stabilize (>5day without power)
DEGA NSx-EL III LCD
110 mA/2,7 W
DEGA NSx-EL III LCD
1-72 h
DEGA NSx-CL III LCD
155 mA/3,7 W
DEGA NSx-CL III LC
max. 1 h
DEGA NSx-IL III LCD
135 mA/3,3 W
DEGA NSx-IL III LCD
max. 30 min
DEGA NSx-SL III LCD
155 mA/3,7 W
DEGA NSx-SL III LCD
max. 5 h
DEGA NSx-PL III LCD
154 mA/3,4 W
DEGA NSx-PL III LCD
max. 30 min
Response time (T90)
Sensor lifetime in a clean environment
DEGA NSx-EL III LCD
max. 180 s -
based on sensor type
DEGA NSx-EL III LCD
2 years
DEGA NSx-CL III LCD
max. 15 s
DEGA NSx-CL III LCD
2 years
DEGA NSx-IL III LCD
max. 15 s
DEGA NSx-IL III LCD
5 years
DEGA NSx-SL III LCD
max. 30 s
DEGA NSx-SL III LCD
2 years
DEGA NSx-PL III LCD
max. 15 s
DEGA NSx-PL III LCD
5 000 h
Operational conditions
Ambient temperature:
-40 °C to +60 °C
Relative humidity:
0-95 % RH
Air pressure:
80-120 kPa
Flow of ambient air:
max. 2 m/s - flow directly to the sensor in not allowed
Protection level with a cover:
IP 54, with a DEGA WATER CAP IP 66 cover
Location:
BE3N2 - explosive atmoshpheres - zone 1 (2 G)
Terminology
The marking system for detector DEGA NSx-yL III LCD:
Gas detector DEGA NSx-yL III LCD
Series of detectors in potentially explosive atmospheres
Type of detected gas
Sensor type with linear output
Third generation product with new DEGA design
Versions with an LCD display
DEGA NSx-EL III LCD with an electrochemical sensor
They operate on the principle of change of electrical parameters on the electrodes stored in electrolyte, due to
oxidation/reduction reactions of the detected gas on it's surface. These sensors have good selectivity and the ability to detect
very low concentrations of toxic gases.
DEGA NSx-CL III LCD with a catalytic sensor (Pelistor)
They operate on the principle of catalytic combustion - gas concentration is measured based on the amount of heat released
in a controlled combustion reaction. The reaction is supported by a suitable temperature and the pressence of a catalyst.
These sensors can be used to detect a broad range of flammable gases. The sensors are characterized by fast response,a long
lifetime and high stability. A minimum of 10 % of Oxygen in the air is required for it's proper function.
DEGA NSx-IL III LCD with an infrared sensor (NDIR)
Top quality scanning method. They operate on the principle of infrared spectroscopy. The sensors have excellent selecivity in
organic matter, do not require any oxygen in the atmoshpere and are resistant to catalyst poisons (sulfur and silicon