5
Â
HVI Conductors
must not be painted in the sealing end range due to the special design of their
outer sheath.
Â
HVI Conductors
with grey sheath may be coated if the following conditions are fulfilled: Lacquers
and paints must be PVC-compatible, may be water-soluble and may contain solvents.
Note
:
Solvents in paints and lacquers quickly evaporate if a thin coat is applied and do not damage pla
-
stics.
Â
When using
HVI Conductors
in hazardous locations, special installation conditions must be obser
-
ved (see installation instructions No. 1501).
Â
The function o
f HVI Conductors
is to maintain the separation distance. Due to their design, they
do not have a magnetic shielding effect. Induction effects in secondary conductors/loops must be
observed. If required, surge protection measures must be taken.
Â
For application-specific questions, please contact the relevant sales team or the DEHN representati
-
ve in your country.
Â
Further information on the component portfolio of the
HVI Conductor system
can be found in our
brochure No. 151, our Lightning Protection/Earthing catalogue or at
www.dehn-international.com
(product data).