10
3.2
HVI Conductor for connection to parts of an installation carrying lightning
voltage
A second sealing end is required to connect the pre-assembled
HVI Conductor
to parts of an installa
-
tion carrying lightning voltage (see 5.3, page 25). To this end, an EB connection element (Part No. 410
229) or a spacer with EB element and MV clamp (Part No. 105 275) must be ordered separately:
HVI Conductor
Part No.
Colour
Installation
Standard/mi-
nimum length
Delivery includes
Types
819 220
819 223
Black
Grey
Inside the
supporting
tube
6 m + x m
LPS II
max. 12.50 m
LPS III/IV
max. 18.75 m
• Pre-assembled HVI Con-
ductor
•
1 fixed head piece cover
-
ed with a heat shrinkable
sleeve
• 1 connection element, 1
heat shrinkable sleeve and
1 hexagon socket wrench
(loose)
819 226
819 227
Black
Grey
Outside the
supporting
tube
Types of EB connec-
tion element
(ordered separately)
410 229
EB connection element
105 275
Spacer with EB element
Field of application
This conductor is used for connecting e.g. several parts of an installation requiring
protection jointly to the earth-termination system of the building via an isolated ring
conductor (see Fig. 17, page 28). Conductors with a sealing end mounted in the supporting
tube and a sealing end to be adjusted on site are typically used whenever the total
conductor length cannot be exactly determined at the design stage of the installation.
Table 4 HVI Conductor
connected to parts of an installation carrying lightning voltage - Overview
Installation inside the supporting tube
Installation outside the supporting tube
HVI Conductor
with special sheath
fixed head piece
Loosely delivered:
- Connection element
- Heat shrinkable sleeve
- Hexagon socket wrench
To be ordered separately:
- EB connection element
(Part No. 410 229)
or
- Spacer with EB element
and MV clamp
(Part No. 105 275)
head piece and
HVI Conductor
covered with a heat shrinkable
sleeve
head piece and
HVI Conductor
covered with a heat shrinkable
sleeve
fixed head piece
HVI Conductor
with special sheath