26
An antenna pipe clamp (Part No. 540 100), for example, can be used to connect the antenna standpipe
to the equipotential bonding system (functional equipotential bonding).
HVI Conductor installed inside in the supporting tube/wall fi xing bracket
Figure 13
Isolated air-termination system with
HVI Conductor
and wall fi xing bracket
protective angle
α
acc. to IEC 62305 Part 3, Table 2
e.g. air termination rod
StSt, Ø 22/16/10 mm, L = 2500 mm
e.g. wall fi xing bracket
StSt, clamping range supporting tube Ø 40-50 mm, with double
cleat, Part No.105 344
double cleat for connecting
2x Rd 8 to 10 mm to the equipotential bonding system
earth connection element
HVI Conductor
connection to the
equipotential bonding
system of the building
earth-termination system
α
α
Sealing and
range
1500 mm
s
supporting tube with air-termination rod
GRP/AL, e.g. Part No. 105 331
supporting tube L = 3200 mm + air-termination rod L = 2500 mm