38
The following versions are available depending on the relevant wind speeds:
Â
Version I
Air-termination tip (Ø 10 mm, L = 1000 mm)
- max. gust wind speed (1 x HVI inside) up to 237 km/h
- max. gust wind speed (4 x HVI outside) up to 197 km/h
Â
Version II
Air-termination rod (Ø 22/16/10 mm, L = 2500 mm)
- max. gust wind speed (1 x HVI inside) up to 190 km/h
- max. gust wind speed (4 x HVI outside) up to 163 km/h
Figure 23
Wind speed – Versions I and II when attaching to the supporting tube
Antenna mast
Antenna
Supporting tube
HVI
long
1000 mm
≤ 2.5 m
≥ 0.5m
2500 mm
α
α
α
α
Connection to
the equipotential
bonding of the
building
Earth-termination system
Version I
Supporting tube with air-termination tip,
e.g. Part No. 105 330 / 105 332, StSt, ø 10 mm, L = 1000 mm
Version II
Supporting tube with air-termination rod,
e.g. Part No. 105 331 /105 333, StSt, ø 22/16/10 mm, L = 2500 mm
≤ 2.5 m
≥ 0.5m