6
Table 2:Technical details of the standard Watermanager GWM*
Description
GWM 500 with booster pump
GWM 500
without booster pump
Item number
813330
813335
Treatment capacity [litre/day]
500
Greywater inlet / overflow
DN 100
Process water overflow
DN 100
Greywater storage tank [litre]
200
Process water storage tank [litre]
600
Connection of coarse filter back-
flush
1/2” female
Drinking water pipe connection
½” female (max. 8,9 m³/h at 5 bar)
Process water pipe connection
(depending on pressure increase)
1” male
1 ½” female
Flow pressure of coarse filter back-
flush / drinking water feed
min. 1 bar; max. 5 bar
Ambient temperature
15°C to 25°C
Mains voltage
230 V AC, 50 Hz, 16 A
Power consumption without pres-
sure increase [watt]
200
Empty weight [kg]
110
Booster pump
Delivery rate
Delivery height
Connection
Power consumption
5,5 m³/h
48 m
1” male
1.100 / 230 V
-
*All shown details may vary depending to specific project details.
Pre-assembled
Watermanager GWM 500
, consisting of:
•
Trident
coarse filter
•
Greywater buffer tank/BMT unit
•
Process water storage tank with integrated drinking water feed facility as per DIN EN 1717 type AB
•
Control unit
•
Air compressor with wall bracket
•
Plastic bag with activated carbon and dried bacteria culture for initial inoculation
•
Assembly accessories
•
Hose connectors
•
Documentation folder
o
Operating instructions
o
Specific set-up diagram
o
Safety data sheet activated carbon/dry bacteria
3.3.
Technical specifications
3.4.
Scope of delivery