Changing the default settings  

The relay contact can be configured to function either as a normally energised contact (NE) or as a 
normally de-energised contact (ND). (The original configuration is marked on the label). 
 
Also  the  maximum  leakage  capacitance  can  be  changed;  dip  switch  settings  are  shown  in 

Fig. 2

Note that this will also change the measuring time. 

 

 
Fig 2. 

 
The illustrations below show the location on the PCB of the S1 switch for selection of either ND or 
NE relay function (dip switch 4). The PCB is located under the rear cover. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Max. leakage capacitance 

Variant no. 

Dip switch 1 

Dip switch 2 

Dip switch 3 

1µF 

01, 02, 03 

N/A 

On 

N/A 

20µF 

01, 02, 03 

N/A 

Off 

N/A 

1µF 

04, 05, 06 

Off 

Off 

Off 

2µF 

04, 05, 06 

On 

Off 

Off 

5µF 

04, 05, 06 

Off 

On 

Off 

10µF 

04, 05, 06 

On 

On 

Off 

20µF 

04, 05, 06 

Off 

Off 

On 

50µF 

04, 05, 06 

On 

Off 

On 

100µF 

04, 05, 06 

Off 

On 

On 

120µF/custom 

04, 05, 06 

On 

On 

On 

 

 

QUICK GUIDE

Insulation monitor, ADL-111Q96 

 

Refer to www.deif.com for detailed information

 

Document no.: 4189330020A 

 

IMPORTANT - use electrostatic discharge protection!  

Sufficient  care  must  be  taken  to  protect  the  PCB  against  static  discharges  during  the 
configuration.  Once  the  unit  is  installed  and  connected,  these  precautions  are  no  longer 
necessary. 