Changing the default settings
The relay contact can be configured to function either as a normally energised contact (NE) or as a
normally de-energised contact (ND). (The original configuration is marked on the label).
Also the maximum leakage capacitance can be changed; dip switch settings are shown in
Fig. 2
.
Note that this will also change the measuring time.
Fig 2.
The illustrations below show the location on the PCB of the S1 switch for selection of either ND or
NE relay function (dip switch 4). The PCB is located under the rear cover.
Max. leakage capacitance
Variant no.
Dip switch 1
Dip switch 2
Dip switch 3
1µF
01, 02, 03
N/A
On
N/A
20µF
01, 02, 03
N/A
Off
N/A
1µF
04, 05, 06
Off
Off
Off
2µF
04, 05, 06
On
Off
Off
5µF
04, 05, 06
Off
On
Off
10µF
04, 05, 06
On
On
Off
20µF
04, 05, 06
Off
Off
On
50µF
04, 05, 06
On
Off
On
100µF
04, 05, 06
Off
On
On
120µF/custom
04, 05, 06
On
On
On
QUICK GUIDE
Insulation monitor, ADL-111Q96
Refer to www.deif.com for detailed information
Document no.: 4189330020A
IMPORTANT - use electrostatic discharge protection!
Sufficient care must be taken to protect the PCB against static discharges during the
configuration. Once the unit is installed and connected, these precautions are no longer
necessary.