Warning Y1W and Y2W
●
Trip Y1T and Y2T
100%
200%
300%
400%
500%
Trip at fixed value 100%
Trip at fixed value 85%
Upper limit
Lower limit
Trip Y1T
Warn. Y1W
Trip Y2T
Warn. Y2W
SP-X1
0%
50%
100%
Adju
stabl
e wa
rning
curv
e
Adj
usta
ble
trip
cur
ve
Id
In
Is
In
6.2.2 Warning (curve 1)
No.
Setting
Min. setting Max. setting Factory setting
1010 Diff. current warning Selection display
-
-
-
1011
Diff. current warning SP-Y value 1 warning, Y1W 5 %
45 %
20 %
1012 Diff. current warning SP-Y value 2 warning, Y2W 25 %
95 %
55 %
1013 Diff. current warning Delay
0.01 s
2.00 s
0.10 s
1014 Diff. current warning Relay output A
R0 (none)
R5 (relay 5)
R3 (relay 3)
1015 Diff. current warning Relay output B
R0 (none)
R5 (relay 5)
R5 (relay 5)
1016 Diff. current warning Enable
OFF
ON
ON
6.2.3 Trip (curve 2)
No.
Setting
Min. setting
Max. setting
Factory setting
1020
Diff. current trip
Selection display
-
-
-
1021
Diff. current trip
SP-X value 1 warn/trip, X1
50 %
300 %
100 %
1022
Diff. current trip
SP-Y value 1 trip, Y1T
5 %
45 %
25 %
1023
Diff. current trip
SP-Y value 2 trip, Y2T
25 %
95 %
70 %
1024
Diff. current trip
Delay
0.01 s
2.00 s
0.10 s
1025
Diff. current trip
Relay output A
R0 (none)
R5 (relay 5)
R4 (relay 4)
1026
Diff. current trip
Relay output B
R0 (none)
R5 (relay 5)
R5 (relay 5)
MDR-2 DRH 4189340300 UK
Parameter programming
DEIF A/S
Page 22 of 26